87
CHAPTER 8 FUNCTION
8
8.8 Scaling Function
(4) Example of scaling setting
Ex.
1: When values are set for a channel with output range of 0 to 5V as follows:
•"CH Scaling enable/disable setting": "0: Enable"
•"CH Scaling upper limit value": 10000
•"CH Scaling lower limit value": 2000
The digital values and scale-converted digital values are as follows:
Digital value
Digital value after scale
conversion
Analog output voltage (V)
2000 0 0
3600 2400 1
5200 4800 2
6800 7200 3
8400 9600 4
10000 12000 5
0V
5V
Scale converted digital value
Analog output voltage (V)
Scaling lower limit
value: 2000
Scaling upper limit
value: 10000
0 12000 12287
Digital value