Mitsubishi Electronics -NZ2GF2B-60DA4 Universal Remote User Manual


 
178
(4) Current output characteristics
The following graph shows the current output characteristics.
*1 Set the offset value and gain value in the user range setting within the range satisfying the following two conditions.
• Setting range: 0 to 20mA
•((Gain value) - (Offset value)) 11.4mA
Use the value within the practical digital input range and practical analog output range. If a value is out of the range, the
maximum resolution and accuracy may not fall within the range of performance specifications. (Do not use the value in the
dotted line region in the above graph.)
No. Output range setting Offset value Gain value Digital value Maximum resolution
1) 4 to 20mA 4mA 20mA
0 to 12000
1.66µA
2) 0 to 20mA 0mA 20mA 1.33µA
-
User range setting 2
(0 to 20mA)
*1 *1 0.95µA
1)
Digital input value
0
0
4
5
10
15
20
6000 12000
12287-288
2)
Analog output
range for
actual use
Analog output
value (mA)