Minor error
Digital value
outside the
range
The value set in CH Digital
value (RWw2 to RWw5) is
outside the range.
represents the channel
number where an error has
occurred.
Set the value of CH Digital value (RWw2 to
RWw5) within the allowable range.
062
H
*1
Moderate error
Alert output
upper/lower
limit value
inverted
The alert output lower limit value
has been set equal to or greater
than the alert output upper limit
value in CH1 Alert output upper
limit value (address: 0106
H
) to
CH4 Alert output lower limit value
(address: 010D
H
).
represents the channel
number where an error has
occurred.
Correct the settings of CH1 Alert output upper
limit value (address: 0106
H
) to CH4 Alert
output lower limit value (address: 010D
H
) so
that the alert output lower limit value is
smaller than the alert output upper limit value.
0730
H
Moderate error
Mode switch
setting error
The value out of range is set in
mode switch (address: 0000
H
).
Reset the mode switch (address: 0000
H
) to
either of the followings.
• Normal mode (0
H
)
• Trigger conversion mode (1
H
)
• Automatical judgment mode (9
H
)
090
H
*1
Moderate error
Scaling setting
outside the
range
The values set in CH1 Scaling
lower limit value (address:
010F
H
) to CH4 Scaling upper
limit value (address: 0116
H
) are
outside the range of -32000 to
32000.
represents the channel
number where an error has
occurred.
Set a value within the range of -32000 to
32000 in CH1 Scaling lower limit value
(address: 010F
H
) to CH4 Scaling upper limit
value (address: 0116
H
).
091
H
*1
Moderate error
Scaling
upper/lower
limit value
inverted
The scaling lower limit value has
been set equal to or greater than
the scaling upper limit value in
CH1 Scaling lower limit value
(address: 010F
H
) to CH4 Scaling
upper limit value (address:
0116
H
).
represents the channel
number where an error has
occurred.
Correct the settings of CH1 Scaling lower limit
value (address: 010F
H
) to CH4 Scaling upper
limit value (address: 0116
H
) so that the
scaling lower limit value is smaller than the
scaling upper limit value.
0920
H
*2
Minor error
Mode switch
setting change
The value set in Mode switch
(address: 0000
H
) has been
changed.
Turn off and on the module so that it operates
according to Mode switch (address: 0000
H
).
0930
H
Moderate error
Cyclic data
update watch
time setting
outside the
range
The value set in Cyclic data
update watch time (address:
0007
H
) is outside the range of 0
to 20.
Set a value within the range of 0 to 20 in
Cyclic data update watch time (address:
0007
H
).
0940
H
Minor error
Station number
switch changed
error
The station number switch setting
has been changed while the
module power is on.
While the module power is on, set the switch
again to the station number that has been set
before.