CHAPTER 8 FUNCTION
8
8.13 CC-Link IE Field Network Synchronous Communication Function
8.13 CC-Link IE Field Network Synchronous Communication
Function
With this function, the D/A converter module can perform D/A conversion synchronized with the operation cycle of a
simple motion module.
This enables the D/A converter module to operate at the same timing of other slave stations on the same network.
This function can be used only when a simple motion module is used for the master station and "Mode switch" is set to "9:
Automatical judgment mode".
(1) Applicable module and software
The table below lists modules and software required to use the CC-Link IE Field Network synchronous
communication function.
(2) Restrictions
This section describes restrictions to use the CC-Link IE Field Network synchronous communication function.
(a) Restrictions to use this function with other functions
(b) Restrictions on the network parameter settings (RWw/RWr)
Set the network parameters (RWw/RWr) so that RWwF/RWrF are assigned to use the synchronous
communication function.
Module and software Serial number (first five digits)/version of GX Works2
D/A converter module "15102" or later
Simple motion module "15092" or later
GX Works2 Version 1.501X or later
Function name Restrictions
Shift function
Cannot be used.
The setting of CH Shifting amount to conversion value (RWw2 to RWw5) will be ignored.
Extension I/O
function
The extension I/O module can be used, but input and output of the extension I/O module is not
synchronized with the operation cycle of the simple motion module.
Cyclic data update
watch function
When the CC-Link IE Field Network synchronous communication function is used, the setting of Cyclic
data update watch time setting (address: 0007
H
) will be ignored.