Mitsubishi Electronics -NZ2GF2B-60DA4 Universal Remote User Manual


 
64
(1) Precautions
(a) Before parameter settings
Read and write the parameter settings of this module with the CPU module in the STOP status. Reading
and writing are unavailable in the RUN status.
Check that the start I/O number of the network parameter of the master station matches that of the PLC
parameter. If they differ, the parameter settings cannot be read or written.
(b) Parameter settings
When using the D/A converter module, enable the block data assurance per station. When it is disabled,
correct operation of the D/A converter module cannot be guaranteed.
For the block data assurance per station, refer to the following.
User's manual for the master/local module used
Do not set the parameter using the CCPASET instruction in the master station. When the CCPASET
instruction is executed, correct operation of the D/A converter module cannot be guaranteed because the
module operates with the block data assurance per station disabled.
When using the extension module, write the module parameter ( Page 65, Section 7.1 (2)). If the
parameter of the extension module has not been written, the error code (1F30
H
) is stored in Latest error
code (RWr0), Error flag (RXA) turns on, and the ERR. LED turns on.
Do not uncheck the box.