Mitsubishi Electronics -NZ2GF2B-60DA4 Universal Remote User Manual


 
26
*1 For details on the I/O conversion characteristics, refer to the following.
• I/O Conversion Characteristic of D/A Conversion ( Page 176, Appendix 4)
*2 Except when receiving noise influence.
*3 Do not connect two or more wires to the terminal.
Applicable
solderless
terminal
Terminal block
for module
power supply
and FG
*3
TE 0.5-10 (Nichifu Co. Ltd.) [Applicable wire size: 0.5mm
2
]
TE 0.75-10 (Nichifu Co. Ltd.) [Applicable wire size: 0.75mm
2
]
TE 1.0-10 (Nichifu Co. Ltd.) [Applicable wire size: 0.9 to 1.0mm
2
]
TE 1.5-10 (Nichifu Co. Ltd.) [Applicable wire size: 1.25 to 1.5mm
2
]
AI 0.5-10WH (Phoenix Contact Co. Ltd.) [Applicable wire size: 0.5mm
2
]
AI 0.75-10GY (Phoenix Contact Co. Ltd.) [Applicable wire size: 0.75mm
2
]
AI 1-10RD (Phoenix Contact Co. Ltd.) [Applicable wire size: 1.0mm
2
]
AI 1.5-10BK (Phoenix Contact Co. Ltd.) [Applicable wire size: 1.5mm
2
]
Terminal block
for analog
output signals
RAV1.25-3 (compliant with JIS C 2805) [Applicable wire size: 0.3 to 1.25mm
2
]
V2-MS3 (JST Mfg. Co., Ltd) [Applicable wire size: 1.25 to 2.0mm
2
]
RAP2-3SL (Nippon Tanshi Co., Ltd.) [Applicable wire size: 1.25 to 2.0mm
2
]
TGV2-3N (Nichifu Co., Ltd.) [Applicable wire size: 1.25 to 2.0mm
2
]
Cyclic
transmission
RX/RY points 32 points + 16 points × number of extension modules
RWr/RWw
points
16 points + points of each extension module
Communication cable
An Ethernet cable that meets the 1000BASE-T standard:
Category 5e or higher (double shielded, STP), straight cable
Availability of connecting
extension module
Connectable (Max. one module)
External power supply
24VDC (20.4 to 28.8VDC)
Inrush current: 30.1A, 1.5ms or less
Current consumption: 325mA
Weight 0.30kg
Item Description