Appendix 7 EMC and Low Voltage Directives
Compliance to the EMC Directive, which is one of the EU Directives, has been a legal obligation for the products sold
in European countries since 1996 as well as the Low Voltage Directive since 1997.
Manufacturers who recognize their products are compliant to the EMC and Low Voltage Directives are required to
attach a "CE mark" on their products.
(1) Sales representative in EU member states
Authorized representative in EU member states is shown below.
Name: Mitsubishi Electric Europe BV
Address: Gothaer Strasse 8, 40880 Ratingen, Germany
Appendix 7.1 Measures to comply with the EMC Directive
The EMC Directive specifies that "products placed on the market must be so constructed that they do not cause
excessive electromagnetic interference (emissions) and are not unduly affected by electromagnetic interference
(immunity)".
This section summarizes the precautions on compliance with the EMC Directive of the machinery constructed with the
module.
These precautions are based on the requirements and the standards of the regulation, however, it does not guarantee
that the entire machinery constructed according to the descriptions will comply with abovementioned directives.
The method and judgement for complying with the EMC Directive must be determined by the person who constructs
the entire machinery.
(1) EMC Directive related standards
(a) Emission requirements
*1 QP: Quasi-peak value, Mean: Average value
*2 The module is an open type device (a device designed to be housed in other equipment) and must be installed inside a
conductive control panel. The tests were conducted with the module installed in a control panel.
Specification Test item Test details Standard value
EN61131-2: 2007
CISPR16-2-3
Radiated emission
*2
Radio waves from the product
are measured.
• 30M-230MHz QP: 40dBµV/m (10m in measurement
range)
*1
• 230M-1000MHz QP: 47dBµV/m (10m in measurement
range)
CISPR16-2-1,
CISPR16-1-2
Conducted
emission
*2
Noise from the product to the
power line is measured.
• 150k-500kHz QP: 79dB, Mean: 66dB
*1