175
APPENDICES
A
Appendix 3 Details of Remote Buffer Memory Areas
(21)Module operation information initialization command (address: 1004
H
)
This command is used to clear the module operation information stored in the nonvolatile memory.
The module operation information can be initialized only when Nonvolatile memory data error (module operation
information) (error code: 0110
H
) has occurred.
(a) Initializing the module operation information
The module operation information is initialized when the value in this area is set to Commanded (1).
(b) Default value
The default value is set to Not commanded (0).
(22)Module operation information initialization completed (address: 1005
H
)
The initialization status of the module operation information stored in a nonvolatile memory is stored.
(a) Initializing the module operation information
When initialization of the module operation information is completed, the value in this area changes to
Completed (1). For the timing of turning the bit Not performed (0) Completed (1) Not performed (0), refer
to the following.
• Module operation information initialization command (address: 1004
H
) ( Page 175, Appendix 3 (21))
(b) Default value
The default value is set to Not performed (0).
Data for b1 to b15 are fixed to "0".
b0b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1
00000000000000 0
0: Not commanded
1: Commanded
Controlled by the D/A converter module
Error data of module operation
Module operation information
initialization command
(address: 1004
H)
Module operation information
initialization completed
(address: 1005
H)
Controlled by the program
Module operation
information
Default value
Not
commanded (0)
Not
commanded (0)
Commanded (1)
Not
performed (0)
Not performed (0)
Completed
(1)
Data for b1 to b15 are fixed to "0".
b0b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1
00000000000000 0
0: Not performed
1: Completed