Mitsubishi Electronics -NZ2GF2B-60DA4 Universal Remote User Manual


 
169
APPENDICES
A
Appendix 3 Details of Remote Buffer Memory Areas
(10)Range setting (address: 0103
H
)
The output range is set for each channel.
(a) Enabling the setting
Turn on and off Initial data setting request flag (RY9).
(b) Default value
The default value is set to 4 to 20mA (0
H
).
If data other than the above is set, an error occurs. The error code (010
H
) is stored in Latest error code (RWr0), Error flag
(RXA) turns on, and the ERR. LED turns on.
(11)Analog output HOLD/CLEAR setting (address: 0104
H
)
Whether to hold or clear the analog value that is output at the state of CPU module being RUN, STOP, or when
an error occurs, is set for each channel.
(a) Enabling the setting
Turn on and off Initial data setting request flag (RY9).
(b) Default value
The default value is CLEAR (0
H
).
Output range Setting value
4 to 20mA
0
H
0 to 20mA
1
H
1 to 5V
2
H
0 to 5V
3
H
-10 to 10V
4
H
User range setting 1 (-10 to 10V)
5
H
User range setting 2 (0 to 20mA)
6
H
Analog output HOLD/CLEAR setting Setting value
CLEAR
0
H
HOLD
1
H
to F
H
(a number other than 0)
b15 to b12 b11 to b8 b7 to b0tob3b4
CH1CH2CH3CH4
b15 to b12 b11 to b8 b7 to b0tob3b4
CH1CH2CH3CH4