HP (Hewlett-Packard) HP 16510B TV Converter Box User Manual


 
You enter a threshold in the pop-up with the keypad by touching the
desired value, units and polarity. When the correct threshold voltage is
displayed, touch DONE. The pop-up will close and the new threshold will
be placed in the pod threshold field.
In the state analyzer, the same threshold level applies to a pod’s clock as
to its 16 data bits.
5Specify
Symbols
The logic analyzer supplies Timing and State Symbol Tables in which
youcandefineamnemonicforaspecificbitpatternofalabel.When
measurements are made by the logic analyzer, the mnemonic is displayed
where the bit pattern occurs if the Symbol base is selected.
It is possible for you to specify up to 200 symbols in the logic analyzer. If
you have only one of the internal analyzers on, all 200 symbols can be
defined in it. If both analyzers are on, the 200 symbols are split between
the two. For example, analyzer 1 may have 150, leaving 50 available for
analyzer 2.
To access the Symbol Table in either the State or Timing Format
Specification menus, touch the Symbols field. You will see a new menu
as shown. This is the default setting for the Symbol Table in both the
timing and state analyzers.
Figure 5-13. Symbol Table Menu
Menus HP 16510B
5-14 Front-Panel Reference