124
19 BUILT-IN I/O FUNCTION
19.1 High-speed Counter Function
High-speed counter (normal mode)
Normal mode for high-speed counters is explained below.
Use normal mode if you want to use as an ordinary high-speed counter.
Set operation mode to normal mode by high-speed counter parameter setting.
Sets detailed settings for channel used.
Navigation window [Parameter] [FX5UCPU] [Module Parameter] [High Speed I/O] “Input Function" “High
Speed Counter" "Detail Setting" “Basic Settings"
Window
Displayed items
Item Description Setting range Default
Use/Not Use Set whether use counter or not. Disable
Enable
Disable
Operation Mode Set operation mode. • Normal Mode
Pulse Density Assumption Mode
Rotation Speed Measurement
Mode
Pulse Input Mode Set pulse input mode. • 1-Phase 1 Input (S/W Up/Down
Switch)
1-Phase 1 Input (H/W Up/Down
Switch)
1 Phase 2 Input
2 Phase 1 Multiple
2 Phase 2 Multiple
2 Phase 4 Multiple
Internal Clock (1MHz)
Preset Input Enable/
Disable
Set whether to "enable" or "disable" the preset input of counter. • Disable
Enable
Input Logic Sets preset input logic when preset input is enabled. • Positive Logic
Negative Logic