Mitsubishi Electronics FX5 Universal Remote User Manual


 
APPENDIX
Appendix 3 Error Code
281
A
33F3H Program
structure error
More than two STL instructions for the
same S number are programmed.
Recheck the structure of the step ladder. Error location
information
At power-on,
at RESET, at
STOP
RUN state
3400H Operation error A value of 0 was input as a divisor in an
applied instruction.
Review the data specified as the divisor in
the applied instruction.
Error location
information
At instruction
execution
3401H Operation error Data that cannot be converted was input
in an applied instruction.
Review the data specified in the applied
instruction.
Error location
information
At instruction
execution
3402H Operation error A value of -0, a denormalized number, a
non-number, or ± was input in an
applied instruction.
Review the data specified in the applied
instruction.
Error location
information
At instruction
execution
3403H Operation error An overflow occurred in an applied
instruction.
Review the data specified in the applied
instruction.
Error location
information
At instruction
execution
3405H Operation error Data that is outside the allowable range
was input in an applied instruction.
Review the data specified in the applied
instruction.
Error location
information
At instruction
execution
3406H Operation error • The output result is outside the allowable
device range in an applied instruction.
Review the data specified in the applied
instruction.
Error location
information
At instruction
execution
3420H Operation error A module access device is specified to
both (s) and (d) in a BMOV instruction.
Review the device specified in the BMOV
instruction.
Error location
information
At instruction
execution
3500H Operation error A value outside the allowable range was
set to the sampling time (TS).
Check the contents of the parameters. Error location
information
At instruction
execution
3502H Operation error A value outside the allowable range was
set to the input filter constant ().
Check the contents of the parameters. Error location
information
At instruction
execution
3503H Operation error A value outside the allowable range was
set to the proportional gain (KP).
Check the contents of the parameters. Error location
information
At instruction
execution
3504H Operation error A value outside the allowable range was
set to the integral time (TI).
Check the contents of the parameters. Error location
information
At instruction
execution
3505H Operation error A value outside the allowable range was
set to the derivative gain (KD).
Check the contents of the parameters. Error location
information
At instruction
execution
35
06H Operation error A value outside the allowable range was
set to the derivative time (TD).
Check the contents of the parameters. Error location
information
At instruction
execution
350AH Operation error The sampling time is lower than the scan
time.
The operation is continued in the condition
"sampling time (TS) = cyclic time (scan
time)".
Error location
information
At instruction
execution
350CH Operation error The variation of measured value is
greater than the maximum value or lower
than the minimum value.
The operation is continued with the
maximum or minimum value.
Error location
information
At instruction
execution
350DH Operation error The deviation is greater than the
maximum value or lower than the
minimum value.
The operation is continued with the
maximum or minimum value.
Error location
information
At instruction
execution
350EH Operation error The integral result is greater than the
maximum value or lower than the
minimum value.
The operation is continued with the
maximum or minimum value.
Error location
information
At instruction
execution
350FH Operation error The derivative value is greater than the
maximum value or lower than the
minimum value due to the derivative gain
(KP).
The operation is continued with the
maximum or minimum value.
Error location
information
At instruction
execution
3510H Operation error The derivative result is greater than the
maximum value or lower than the
minimum value.
The operation is continued with the
maximum or minimum value.
Error location
information
At instruction
execution
3511H Operation error The PID operation result is greater than
the maximum value or lower than the
minimum value.
The operation is continued with the
maximum or minimum value.
Error location
information
At instruction
execution
3512H Operation error The output upper limit value is lower than
the output lower limit value.
Calculation is continued with the output
upper limit value and output lower limit value
transposed.
Error location
information
At instruction
execution
3513H Operation error The input variation alarm set value or
output variation alarm set value is
outside the allowable range.
The operation is continued without alarm
output.
Error location
information
At instruction
execution
Error
code
Error name Error details and cause Action Detailed
information
Diagnostic
timing