Mitsubishi Electronics FX5 Universal Remote User Manual


 
132
19 BUILT-IN I/O FUNCTION
19.1 High-speed Counter Function
High-speed comparison table
The high-speed comparison table is explained below.
Used to set high-speed comparison table for high-speed counters.
Sets match output setting for high-speed counters.
Navigation window [Parameter] [FX5UCPU] [Module Parameter] [High Speed I/O] “Input Function" “High
Speed Counter" "Detail Setting" “High Speed Compare Table"
Window
Displayed items
You can create an open table entry before table setting is complete.
Table settings can be made in any order. Be careful when the current value is changed by self-reset at a
table along the way, as table processing starts with the first table then the following tables in order.
High-speed comparison table operation
Operation of each type of high-speed comparison table operation is explained below.
Set to ON
When comparison value 1 matches the current value of the set high-speed counter, the bit device specified as the output
destination device is set. If interrupt pointer has been specified for output destination device, the interrupt program of the
specified interrupt pointer is run simultaneously when it matches comparison value 1.
Operation is the same as for the DHSCS instruction. For information on the DHSCS instruction, refer to MELSEC iQ-F
FX5 Programming Manual (Instructions, Standard Functions/Function Blocks).
Item Description Setting range Default
Counter CH Set the counter CH of coincidence output target. Disable, CH1 to CH8 Disable
Comparison Type Set comparison type. • Set
Reset
Self Reset
Band Area Comparison
Set
Output Destination Device Sets output destination device for output comparison
results of comparison value 1 and comparison value 2.
Bit device (Y, M), Interrupt pointer (I16 to I23)
Comparison Value 1
Specification Method
Sets the specification method of comparison value 1. • Direct Specification
Indirect Specification
Direct
Specificati
on
Comparison Value 1 Direct Sets value (comparison value 1) to be compared with
current value of high-speed counter. (When direct
specification is selected)
-2147483648Comparison value 1+2147483647 0
Comparison Value 1 Indirect Sets device (comparison value 1) to be compared with
current value of high-speed counter. (When indirect
specification is selected)
Word device (D, R)
Comparison Value 2
Specification Method
If band comparison is set to comparison type, sets the
specification method of comparison value 2.
Direct Specification
Indirect Specification
Comparison Value 2 Direct If band comparison is set to comparison type, sets value
(comparison value 2) to be compared with current value
of high-speed counter. (When direct specification is
selected)
Comparison value 1Comparison value
2+2147483647
Comparison Value 2 Indirect If band comparison is set to comparison type, sets
device (comparison value 2) to be compared with
current value of high-speed counter. (When indirect
specification is selected)
Word device (D, R)