10 CONSTANT SCAN
10.1 Constant scan settings
85
10
Conditions of setting time
Set a value that meets the following relational equation for the setting time of the constant scan.
"WDT setting time" > "Constant scan setting time" > "Maximum scan time of the program"
When the maximum scan time of the program is longer than the setting time of the constant scan, it results in error. The
constant scan time is ignored and it is executed with the scan time of the program.
Ex.
When the constant scan time is set to 4 ms
Wait time from the execution of END process until the beginning of the next scan
When there is a processing mentioned below requested during wait time, the processing of the program is interrupted and the
corresponding process is carried out.
Interrupt program
Event execution type program which triggers the generation of interruption
Device/label access service processing
END 0 END 0 END 0 END 0
1 ms
2 ms
1 ms 1 ms
2 ms
1 ms 1 ms
4 ms4 ms5.3 ms4 ms
0
1
2
Constant scan (4 ms)
3412345 12341234 ms
1 ms
2 ms
Scan where the constant scan setting is not applied