4/00 UDC 3300 Process Controller Product Manual 91
Lower Display
Prompt
Upper Display
Range of Setting
or Selection
Parameter
Definition
AT ERROR
or
AT ERR 2
(depending on loop)
Read Only
RUNING
NONE
OUTLIM*
IDFAIL*
ABORT
LOW PV*
ACCUTUNE ERROR STATUSWhen an error is
detected in the Accutune process, an error prompt will
appear.
RUNNINGAn Accutune process is still active checking
process gain, even though “T” is not lit. It does not affect
keyboard operation.
NONENo errors occurred during last Accutune
procedure.
OUTPUT REACHED LIMITS (HIGH OR LOW)Output
set insufficiently to get to SP value.
ATTENTION
This error will cause the controller to switch
from Automatic to Manual mode. The output is then set to
the value present at the beginning of the Accutune
process.
IDENTIFICATION PROCESS FAILEDAn illegal value
for Gain, Rate, or Reset was calculated.
CURRENT ACCUTUNE PROCESS ABORTEDCaused
by one of the following conditions:
changing to manual mode
digital input detected
changing SP while PV (error) tune in progress
in heat region of output but a cool output is
calculated, or vice versa.
LOW PVPV not changed sufficiently or the PV has
increased by more than 4 % and Deadtime not
determined.
*Applies to SP and SP+PV tuning only.