56 UDC 3300 Process Controller Product Manual 4/00
3.13 Input 2 Parameters Set Up Group
Introduction
This data deals with various parameters required to configure Input 2.
Function prompts
Table 3-10 lists all the function prompts in the Input 2 Set Up group.
Table 3-10 Input 2 Group Function Prompts
Function Prompt
Lower Display
Function
Name
Selections or
Range of Setting
Upper Display
Factory
Setting
Refer
to
IN2 TYPE
Input 2 Actuation Type DISABL NM90 L 500 PT
B TC NIC TC RAD RH
E TC H R TC RAD RI
E TC L S TC 0-20mA
J TC H T TC H 4-20mA
J TC L T TC L 0-10mV
K TC H W TC H 0-50mV
K TC L W TC L 0-5 V
NNM H 100 PT 1-5 V
NNM L 100 LO 0-10 V
NM90 H 200 PT SLIDEW
0-10mV
Section
4.9
XMITTER2
Transmitter Characterization B TC S TC
E TC H T TC H
E TC L T TC L
J TC H W TC H
J TC L W TC L
K TC H 100 PT
K TC L 100 LO
NNM H 200 PT
NNM L 500 PT
NM90 H RAD RH
NM90 L RAD RI
NIC TC LINEAR
R TC SQROOT
ANALYT*
LINEAR
ANALYTIC*
Analytic Selections
XMITTER2 must be set to
ANALYT for this prompt to
appear
NONE
PH
ORP mV
CONDmS
CONDuS
RSTVM^
TDS PPm
TDS PPb
CONCPt
DO PPm
DO PPb
NONE
IN2 HI
Input 2 High Range Value
(Linear Inputs only)
–999. to 9999. floating
(in engineering units)
1000
IN2 LO
Input 2 Low Range Value
(Linear Inputs only)
–999. to 9999. floating
(in engineering units)
0
RATIO 2
Input 2 Ratio –20.00 to 20.00 1.000
BIAS IN2
Input 2 Bias –999. to 9999.
(in engineering units)
0
FILTER 2
Input 2 Filter 0 to 120 seconds 0
BURNOUT2
Burnout Protection NONE
UP
DOWN
NO_FS
NONE
EMISSIV2
Emissivity 0.01 to 1.00 0.00
*Not available on DC330B