Honeywell UDC 3300 Universal Remote User Manual


 
162 UDC 3300 Controller Product Manual 4/00
Enabling (or disabling)
the remote setpoint
Use the procedure in Table 5-12 to enable the remote setpoint source.
Table 5-12 Procedure for Enabling (or Disabling) the Remote Setpoint
Step Operation Press Action
1
Select Set Up
Group
SET UP
until you see:
CONTROL
Lower Display
SET UP
Upper Display
CONTROL2
Lower Display
SET UP
Upper Display
for Loop 1 for Loop 2or
2
Select the
Remote Setpoint
Source prompt
FUNCTION
LOOP 1/2
Until you see:
Lower Display
Upper Display
RSP SRC
The Remote Setpoint
source selection
NONE—not used
INP 2—Input 2 as RSP
IN AL1—Input algorithm 1
IN AL2—Input algorithm 2
INP 3—Input 3 as RSP
3
Change
selection
or
to enable or disable the remote setpoint.
ATTENTION
You cannot change the
remote setpoint value using these keys.
4
Return to normal
operation
LOWER
DISPLAY
This will return the controller to normal
operation.
Setpoint selection
indication
Table 5-13 shows how the indicators react and what the displays show for
each type of setpoint.
Table 5-13 Setpoint Selection Indication
Using Local
Setpoint
Using Remote
Setpoint
Using 2nd
Local
Setpoint
Using 3rd
Local
Setpoint
SP RSP 2SP 3SP
Upper
Display
PV and the PV
value
PV and the PV
value
PV and the PV
value
PV and the PV
value
Lower
Display
SP and the
Local Setpoint
Source
RSP and
Remote Setpoint
Value
2SP and the
2nd Local
Setpoint Value
3SP and the
3rd Local
Setpoint Value
Annunciator None
"
" lights "" lights "3" lights