Honeywell UDC 3300 Universal Remote User Manual


 
58 UDC 3300 Process Controller Product Manual 4/00
3.15 Loop 1 Control Parameters Set Up Group
Introduction
The functions listed in this group define how the Single Loop process
controller or Loop 1 of a Two Loop process controller will control the
process.
Function prompts
Table 3-12 lists all the function prompts in the Control Set Up group.
Table 3-12 Control Group Function Prompts
Function Prompt
Lower Display
Function
Name
Selections or
Range of Setting
Upper Display
Factory
Setting
Refer
to
PV SOURC
Process Variable Source INP 1 IN AL1 INP 3
INP 2 IN AL2
INP 1
Section
4.11
PID SETS
Tuning Parameter Sets 1 ONLY
2KEYBD
2PV SW
2SP SW
GAIN S (Gain scheduling
automatically disables Accutune for
this loop)
1 ONLY
SW VALUE
Automatic Switchover Value Value in engineering units within PV
or SP range limits
0.00
LSP’S
Local Setpoint Source 1 ONLY
TWO
THREE (Selection automatically
disables RSP SRC)
1 ONLY
RSP SRC
Remote Setpoint Source NONE IN AL1 INP 3
INP 2 IN AL2
NONE
AUTOBIAS
Automatic Bias ENABLE
DISABL
DISABL
SP TRACK
Local Setpoint Tracking NONE
PV
RSP
NONE
PWR MODE
Power Up Mode Recall MANUAL
A LSP
A RSP
AM SP
AM LSP
MANUAL
PWR OUT
TPSC Output Start-up Mode LAST
F’SAFE
LAST
SP HiLIM
Setpoint High Limit 0 to 100 % of span input in
engineering units
1000
SP LoLIM
Setpoint Low Limit 0 to 100 % of span input in
engineering units
0
ACTION
Control Output Direction DIRECT
REVRSE
REVRSE