Step
Press
SET
UP
to Select Set
Up Group
Press
FUNC
to
Select
Function
Prompts
Press
▲ ▼
to Enter
Value or
Selection
Remarks
4 Algorithm
CONT ALG PID A Defines back-up control algorithm.
5 Tuning
RSET2MIN 50.00
GAIN2 See Note 1 Note 1. Set the Gain 2 equal to
Input 1 Span
Input 2 Span
If “PB” is selected under the Control Set Up group
function prompt PBorGAIN, set the PROP BD2 to
100 x
Input 2 Span
Input 1 Span
RATE2MIN 0.00 Select PIDSET 1 tuning parameters as needed by the
application.
6 Options
DIG IN1 or
DIG IN2
AM STA
CAUTION
DO NOT SELECT
In the CONTROL set up list, do not select SP TRACK as PV or RSP.
In the SP RAMP set up list, do not select SP RATE as ENABLE.
In the ALGORTHM set up list, do not select CONT ALG as
PID B, ON-OFF, or 3PSTEP.
In the Display menu when PIDSET # is displayed, DO NOT change the
selection.
Operation
Set the local setpoint 2 to 0 % of the Input 2 range.
These features work with the Auto/Manual Station.
In the SP RAMP set up list, SP PROG (acts on SP1 for backup
operation).
In the SP RAMP set up list, SP RAMP (acts on SP1 for backup
operation).
In the CONTROL set up list, ACTION as DIRECT or REVERSE for
the backup PID A operation.
The PD+MR action is forced to be DIRECT as required for the pass
through of the output signal.