Honeywell UDC 3300 Universal Remote User Manual


 
212 UDC 3300 Controller Product Manual 4/00
Table 6-2 Prompt Hierarchy and Available Selections
Prompt
(Lower
Display)
Definition Value or Selection (use or )
(Upper Display)
SP RAMP
Setpoint Ramp Selection Selections: DISABL
SP RAMP must be disabled to allow
Setpoint Programming.
SP RATE
Setpoint Rate of Change Selections: DISABL
SP RATE must be disabled to allow
Setpoint Programming.
SP PROG
Setpoint Ramp/Soak
Programmer
Selections:
DISABL
ENABLE—Loop 1
ENABL2—Loop 2
ENAB12—Loops 1 and 2
SP PROG must be enabled to view
the remaining prompts.
STRT SEG
Start Segment Number Enter Value: 1 to 11
END SEG
End Segment Number Enter Value: 2 to 12
Always end in a soak Segment
(2,4,.....12)
RAMPUNIT
Engineering Units from
Ramp Segments
Selections:TIME
EU/MIN
EU/HR
RECYCLES
Number of Program
Recycles
Enter Value: 0 to 99 recycles
SOAK DEV
Guaranteed Soak Deviation
Value
Enter Value: 0 to +99.00
The number selected will be
0 to 99 ± from setpoint.
PROG END
Program Termination State Selections: LASTSP—Hold at
last setpoint in the
program
F SAFE—Manual
mode/Failsafe
output
STATE
Program State at Program
End
Selections: DISABL
HOLD (hold mode)
KEYRESET
Reset/rerun SP Program Selections: DISABL
RERUN
TOBEGN
HOTSTART
PV Hot Start
Program Initialization or
power up in SPP
Selections: DISABL—LSP1 is
used as the initial
ramp setpoint.
ENABL—PV value is
used as the initial
ramp setpoint.
SEG1RAMP
or
SEG1RATE
Segment #1 Ramp Time
or
Segment #1 Ramp Rate
Enter Value:
Ramp Time = 0-99hr.0-59min, or
Ramp Rate = Engineering units/min
or Engineering units/hr
Select TIME, EU/MIN, or EU/HR at
prompt RAMP UNIT. All ramps will
use the same selection.