Two-loop restrictions
Table 5-23 gives two-loop functionality and restrictions for controllers
with two current outputs (including Auxiliary output) and two relay
outputs.
Table 5-23 Two-loop Functionality and Restrictions (Model DC330E-KE-2XX or
Model DC330E-KE-5XX)
Controller with Two Current Outputs (including Auxiliary Output) and Three Relay Outputs
Output Type Current Auxiliary Relay #1 Relay #2 Relay #3
Loop 1 is TIME SIMPLEX,
Loop 2 is:
Time Simplex
Current or Current Duplex (100 %)
Current/Time or Time/Current
Not used
Not used
Not used
Not used
Loop 2 Output
Loop 2:
Output 1 or 2
N/A
N/A
N/A
Loop 1 Output
Loop 1 Output
Loop 1 Output
Loop 2 Output
Alarm 1
Loop 2:
Output 1 or 2
Loop 1 is TIME DUPLEX/TPSC,
Loop 2 is:
Time Simplex (N/A)
Current or Current Duplex (100 %)
Current/Time or Time/Current (N/A)
Not used
Loop 2 Output
N/A
Loop 1,Output 1
Loop 1,Output 2
Loop 1 is CURRENT OUTPUT or
CURRENT DUPLEX 100 %,
Loop 2 is:
Time Simplex
Current or Current Duplex (100 %)
Current/Time or Time/Current (N/A)
Loop 1 Output
Loop 1 Output
Loop 1 Output
Not used
Loop 2 Ouptut
Loop 2:
Output 1 or 2
N/A
N/A
N/A
Loop 2 Output
Alarm 2
Loop 2:
Output 1 or 2
Alarm 1
Alarm 1
Alarm 1
Loop 1 is CURRENT DUPLEX 50 %,
Loop 2 is:
Time Simplex
Current (N/A)
Current/Time or Time/Current (N/A)
Loop 1,Output 1
Loop 1,Output 2
N/A
Loop 2 Output
Alarm 1
Loop 1 is TIME/CURRENT or
CURRENT/TIME,
Loop 2 is:
Time Simplex
Current or Current Duplex (100 %)
Current/Time or Time/Current
Loop 1:
Output 1 or 2
Loop 1:
Output 1 or 2
Loop 1:
Output 1 or 2
Not used
Loop 2 Output
Loop 2:
Output 1 or 2
N/A
N/A
N/A
Loop 1:
Ouptut 1 or 2
Loop 1:
Output 1 or 2
Loop 1:
Output 1 or 2
Loop 2 Output
Alarm 1
Loop 2:
Output 1 or 2
TWO-LOOP RESTRICTIONS:
1. Time Duplex and Three Position Step Control are not available on Control Loop 2.
2. Position Proportional Control is not available on Two-Loop or Cascade Controllers.
3. If either Time Duplex or Three Position Step Control is selected as Control Loop 1 Output, then Time Simplex,
Current/Time Duplex and Time/Current Duplex are not available for Control Loop 2 Output.
4. Current Duplex 50 % is not available on Model No. DC330E-EE-2XX.