Honeywell UDC 3300 Universal Remote User Manual


 
130 UDC 3300 Process Controller Product Manual 4/00
Lower Display
Prompt
Upper Display
Range of Setting
or Selection
Parameter
Definition
AUX OUT
DEV
DEVIATION (PROCESS VARIABLE MINUS
SETPOINT)Represents 100 % to +100 % of the
selected PV span in engineering units.
FOR EXAMPLE:
Type T Thermocouple
PV range = 300 °F to +700 °F
PV span = 1000 °F
Deviation Range = 1000 °F to +1000 °F
If PV = 500 °F
and SP = 650 °F
then Deviation Display = 150 °F
Auxiliary Output = 42.5 %
When Deviation is selected, only one operating parameter
will be entered. This value represents the deviation level
that will produce 20 mA (100 %) output. Zero deviation will
produce a center scale (12 mA or 50 %) output. A
negative deviation equal in magnitude to the auxiliary
output high value will produce a low end (4 mA or 0 %)
output.
OUTPUT OUTPUTRepresents the displayed controller Loop 1
output in percent (%). Cannot be used with
3 Position Step Control.
SP SETPOINTRepresents the Loop1 value of the setpoint
in units of PV.
LSP 1 LOCAL SETPOINT ONEAuxiliary output represents
Loop1 local setpoint one regardless of active setpoint.
IN AL1 INPUT ALGORITHM 1 OUTPUTRepresents the output
from input algorithm 1.
IN AL2 INPUT ALGORITHM 2 OUTPUTRepresents the output
from input algorithm 2.
PV2 PROCESS VARIABLE 2Represents the value of the
Process Variable for Loop 2.
DEV 2
DEVIATION 2 (PROCESS VARIABLE MINUS
SETPOINT)Represents 100 % to +100 % of the
selected PV span in engineering units for Loop 2.
When Deviation is selected, only one operating parameter
will be entered. This value represents the deviation level
that will produce 20 mA (100 %) output. Zero deviation will
produce a center scale (12 mA or 50 %) output. A
negative deviation equal in magnitude to the auxiliary
output high value will produce a low end (4 mA or 0 %)
output.
OUTPT2 OUTPUT 2Represents the displayed controller output in
percent (%) for Loop 2.
SP L2 SETPOINT 2Represents the value of the setpoint in
units of PV for Loop 2.
LSP1 2 LOCAL SETPOINT 2Represents the value of local
setpoint #1 in units of PV for Loop 2.