4/00 UDC 3300 Process Controller Product Manual 47
3.9 Accutune Set Up Group
Introduction
The Accutune Set Up group offers these selections:
FUZZY
Fuzzy Overshoot Suppression—Uses fuzzy logic to suppress or
eliminate any overshoot that may occur when the PV approaches
setpoint.
TUNE
Demand Tuning—The tuning process is initiated through the operator
interface keys or via a digital input (if configured). The algorithm then
calculates new tuning parameters and enters them in the tuning group.
TUNE does operate with 3 Position Step Control.
SP*
SP Tuning—SP tuning continuously adjusts the PID parameters in
response to setpoint changes. You can select tuning on minimum
setpoint changes of 5 % up to 15 % span. Perform SP tuning after you
have configured the controller.
SP tuning does not operate with 3 Position Step Control algorithm.
TUN+PV*
or
SP+PV*
PV Tuning—The (TUNE) Demand Tuning or the (SP) Setpoint
Tuning portions of these selections work as stated above. PV Adapt
will occur during Process Variable (PV) disturbances (0.3 % span or
larger) which result from non-linearities, process dynamics, load
changes, or other operating conditions. When this condition exists, the
controller monitors the process response for 1 and 1/2 process cycles
around the setpoint to determine whether there has been a true process
change or a momentary upset.
Process retuning occurs as the process dynamics are learned. When the
process is being learned with possible retune, a t is shown in the upper
left display digit.
*SP + PV Tuning not available on Basic Model DC330B.