Honeywell UDC 3300 Universal Remote User Manual


 
118 UDC 3300 Process Controller Product Manual 4/00
4.11 Loop 1 Control Parameters Set Up Group
Introduction
The functions listed in this group deal with how the Single-Loop process
controller or Loop 1 of a Two-Loop process controller will control the
process including: PV source, Number of tuning parameter sets, Setpoint
source, Tracking, Power-up recall, Setpoint limits, Output direction, rate
and limits, Power-up preset outputs, Dropoff, Deadband, and Hysteresis.
Control group
prompts
Table 4-10 lists all the function prompts in the Control Set Up group and
their definitions.
Table 4-10 Control Group Definitions
Lower Display
Prompt
Upper Display
Range of Setting
or Selection
Parameter
Definition
PV SOURCE
INP 1
INP 2
IN AL1
IN AL2
INP 3
PROCESS VARIABLE SOURCE Select the source of
the Process Variable.
INPUT 1
INPUT 2
INPUT ALGORITHM 1
INPUT ALGORITHM 2
INPUT 3
PID SETS
NUMBER OF TUNING PARAMETER SETSThis
selection lets you choose one or two sets of tuning
constants (gain, rate, and reset).
1 ONLY ONE SET ONLYOnly one set of tuning parameters is
available. Configure the values for:
Gain (proportional band),
Rate,
Reset Time, and
Cycle Time (if time proportional is used).
2KEYBD TWO SETS KEYBOARD SELECTABLETwo sets of
tuning parameters can be configured and can be selected
at the operator interface or by using the Digital Inputs.
Press LOWER DISPLAY
key until you see PID SET1 or
PID SET2 then press
or to switch between
sets. Configure the values for:
Gain, Rate, Reset, Cycle Time
Gain #2, Rate #2, Reset #2, Cycle #2 Time
See Subsection 5.10 for procedures.