4/00 UDC 3300 Process Controller Product Manual 49
3.10 Algorithm Data Set Up Group
Introduction
This data deals with various algorithms residing in the controller:
Control algorithms,
Input Math algorithms,
selecting the 1 or 2 PID Loops,
Output Override,
2 Eight Segment Characterizers,
the Timer function, and
Totalizer function.
Gain Scheduler
ATTENTION
Math option (two algorithms, two characterizers,
totalizer) and Two Loops of Control are only available on Expanded
Model DC330E.
Function prompts
Table 3-7 lists all the function prompts in the Algorithm Set Up group.
Table 3-7 Algorithm Group Function Prompts
Function Prompt
Lower Display
Function
Name
Selections or
Range of Setting
Upper Display
Factory
Setting
Refer
to
CONT ALG
Control Algorithm ON-OFF
PID A
PID B
PD+MR
3PSTEP
PID A
Section
4.6
PIDLOOPS
(NOTE 1)
PID Loop Selection 1 LOOP
2LOOPS
CASCAD
1 or 2
CONT2ALG
(NOTE 1)
Control 2 Algorithm PID A
PID B
PD+MR
PID A
OUT OVRD
(NOTE 2)
Output Override Select DISABL
HI SEL
LO SEL
DISABL
TIMER
Timer Enable/Disable ENABLE
DISABL
DISABL
PERIOD*
Timeout Period 00:00 to 99:59 00:01
START*
Start Initiation KEY (Run/Hold key)
ALARM2
KEY
L DISP*
Lower Display Selection TI REM (time remaining)
E time (elapsed time)
TI REM
*Prompt appears only when Timer is enabled.
NOTE 1: Two Loops and Cascade are only available on Expanded Model DC330E.
NOTE 2: Does not apply to Three Position Step Control.