6.5 Run/Monitor the Program
Introduction
Make sure all the SP PROG function prompts under the Set Up group
SP RAMP have been configured with the required data.
An “H” will appear in the upper display indicating that the program is in
the HOLD state.
Run/monitor functions
Table 6-3 lists all the functions required to run and monitor the program.
Table 6-3 Run/Monitor Functions
Function Press Result
Set the Local
Setpoint
SETPOINT
SELECT
You will see
SP
Lower Display
Upper Display
Local Setpoint Value
or
to set the Local Setpoint value to where you
want the program to start out.
Run State
RUN
HOLD
Initiates the setpoint program.
An R appears in the upper display
indicating that the program is running.
Hold State
RUN
HOLD
Holds the setpoint program. An H appears
in the upper display indicating that the
program is in the HOLD state.
The setpoint holds at the current setpoint.
External Hold
DI = To Hold
If Remote Switching (Digital Input option) is
present on your controller, contact closure
places the controller in the HOLD state, if the
setpoint program is running. The H in the
upper display will blink indicating external
hold is in effect.
ATTENTION
The keyboard takes
priority over external switch for the
RUN/HOLD function.
Contact reopening runs program.
Changing a Segment
while in Hold
or
These keys will operate and allow you to
change the segment number while in HOLD.
If a different segment is selected, it will be
started at the beginning when placed in
RUN. If the original segment is brought back,
the program will continue from the point
placed in HOLD.
NOTE: Changing a segment number may
affect the alarms/events.