4/00 UDC 3300 Process Controller Product Manual 137
Lower Display
Prompt
Upper Display
Range of Setting
or Selection
Parameter
Definition
SHEDMODE
LAST
TOAUTO
FSAFE
To MAN
SHED CONTROLLER MODE AND OUTPUT LEVEL
Determines the mode of local control you want when the
controller is shed from the communications link.
Note: If COMSTATE = MODBUS or MB3K and if
SHEDENAB=DISABLE, this prompt will not be
configurable.
LASTSAME MODE AND OUTPUTThe controller will
return to the same mode (manual or automatic) at the
same output level that it had before shed.
ToAUTOAUTOMATIC MODE, LAST SPThe controller
will return to the automatic mode and the last setpoint
used before shed.
FSAFEMANUAL MODE, FAILSAFE OUTPUTThe
controller will return to manual mode at the output value
selected at Control prompt FAILSAFE.
TO MANMANUAL MODE, SAME OUTPUTThe
controller will return to manual mode at the same output
level that it had before shed.
SHED SP
TO LSP
TO CSP
SHED SETPOINT RECALL
Note: If COMSTATE = MODBUS or MOD3K and if
SHEDENAB=DISABLE, this prompt will not be
configurable.
TO LSPController will use last local or remote setpoint
used.
TO CSPWhen in “slave” mode, the controller will store
the last host computer setpoint and use it at the Local
setpoint. When in monitor mode, the controller will shed
to the last UDC Local or Remote setpoint used, and the
LSP is unchanged.
UNITS
(RS422/485 ASCII only)
PERCNT
ENG
COMMUNICATION UNITSThis selection determines
how the controller values are expressed (on both loops)
during communications.
PERCENT OF SPAN
ENGINEERING UNITS
CSP RATO
20.0 to 20.0 LOOP 1 COMPUTER SETPOINT RATIOComputer
setpoint ratio for Loop 1.
CSP BIAS
999. to 9999.
(engineering units)
LOOP 1 COMPUTER SETPOINT BIASComputer
setpoint bias for Loop 1.
CSP2RATO
20.0 to 20.0 LOOP 2 COMPUTER SETPOINT RATIOComputer
setpoint ratio for Loop 2.
CSP2BIAS
999. to 9999
(engineering units)
LOOP 2 COMPUTER SETPOINT BIASComputer
setpoint bias for Loop 2.