Honeywell UDC 3300 Universal Remote User Manual


 
108 UDC 3300 Process Controller Product Manual 4/00
Lower Display
Prompt
Upper Display
Range of Setting
or Selection
Parameter
Definition
TOT RATE
SECOND
MINUTE
HOUR
DAY
ML/DAY
TOTALIZER INTEGRATION RATEDetermines the rate
at which the Totalizer is updated.
SECONDEngineering units per second
MINUTEEngineering units per minute
HOUREngineering units per hour
DAYEngineering units per day
MIL/DAYMillions of units per day
ATTENTION
The source of the Totalizer is averaged
over the sample and update rates. For example, since the
loop cycle speed is six per second, then with the Totalizer
Rate set at once per minute, the source is averaged six
times per second and the Totalizer value is updated with
this average value ÷ 60 once per second.
NOTE 1: Does not apply to Three Position Step Control.
NOTE 2. If the calculated value of the quantity under the square root sign decreases to a value less than 0.010, the
calculation will become linear as the calculated value decreases below 0.010.
*Where: K = 0.001 to 1000 (configurable)
Calc Hi and Calc Lo are configurable over a range of 999 to 9999