4/00 UDC 3300 Process Controller Product Manual 99
Lower Display
Prompt
Upper Display
Range of Setting
or Selection
Parameter
Definition
ALG1 INA
INP 1
INP 2
LP1OUT
LP2OUT
IN AL1
IN AL2
INP 3
ALGORITHM 1, INPUT A SELECTION will represent one
of the available selections.
Input 1
Input 2
Output 1 (NOTE 1)
Output 2
Input Algorithm 1
Input Algorithm 2
Input 3
ALG1 INB
INP 1
INP 2
LP1OUT
LP2OUT
IN AL1
IN AL2
INP 3
ALGORITHM 1, INPUT B SELECTION will represent one
of the available selections.
Input 1
Input 2
Output 1 (NOTE 1)
Output 2
Input Algorithm 1
Input Algorithm 2
Input 3
ALG1 INC
NONE
INP 1
INP 2
LP1OUT
LP2OUT
IN AL1
IN AL2
INP 3
ALGORITHM 1, INPUT C SELECTION will represent one
of the available selections.
None
Input 1
Input 2
Output 1 (NOTE 1)
Output 2
Input Algorithm 1
Input Algorithm 2
Input 3
PCO SEL
DISABL
ONLINE
PERCENT CARBON SOURCE allows a live Input 3 value
to be substituted for the static % CO value (PCT CO).
DISABLED
ONLINEInput 3 must be enabled
PCT CO
0.020 to 0.350 (fractional
percent of CO)
PERCENT CARBON is only applicable when Carbon
Potential is selected. Enter the value in percent carbon
monoxide that is applicable for the enriching gas used in
fractional form.
FOR EXAMPLE:
Natural Gas = 20.0 % CO, then setting is 0.200
Propane Gas = 23.0 % CO, setting is 0.230
ATM PRES
590.0 to 760.0 (mm Hg) ATMOSPHERIC PRESSURE COMPENSATION is only
applicable when Relative Humidity is selected. Enter the
value of the atmospheric pressure of the process.
ALG1 BIAS
-999 to 9999 floating (in
engineering units)
INPUT ALGORITHM 1 BIASDoes not apply to
selections: FFWRD, FFWDM2, HISEL, or LOSEL.