178 UDC 3300 Controller Product Manual 4/00
Step Operation Press Action
3
Select Loop 2
algorithms
FUNCTION
LOOP 1/2
until you see:
OUT2 ALG
Lower Display
Upper Display
NONE
TIME
CURRNT
CUR D
CUR TI
TI CUR
or
to select Loop 2 algorithm.
Select control
parameters for each
loop
The procedure in Table 5-26 shows you how select the 2 loop algorithm.
Table 5-26 Procedure for Selecting Control Parameters
Step Operation Press Action
1
Select Control
Set Up Group
SET UP
until you see:
CONTROL
Lower Display
SET UP
Upper Display
CONTROL2
Lower Display
SET UP
Upper Display
for Loop 1 for Loop 2or
2
Refer to Section 5.12 for rules and
restrictions and to Section 3 Configuration
to select the individual parameters.