40 UDC 3300 Process Controller Product Manual 4/00
3.5 Configuration Procedure
Introduction
Each of the Set Up groups and their functions are pre-configured at the
factory.
The factory settings are shown in Tables 3-3 through 3-18 which follow
this procedure.
If you want to change any of these selections or values, follow the
procedure in Table 3-2. This procedure tells you the keys to press to get to
any Set Up group and any associated Function parameter prompt.
If you need a detailed explanation of any prompt, refer to Section 4 –
Configuration Parameter Definitions.
Procedure
Follow the procedure listed in Table 3-2 to access the Set Up groups and
Function prompts.
ATTENTION The prompting scrolls at a rate of 2/3 seconds when the
SET UP or FUNCTION key is held in. Also, [ ] [ ] keys will move
group prompts forward or backward at a rate twice as fast.
Table 3-2 Configuration Procedure
Step Operation Press Result
1
Select Set Up mode
SET UP
SET UP
Upper Display
Lets you know you are in the
configuration mode and a Set Up group
title is being displayed in the lower
display.
TUNING *
Lower Display
This is the first Set Up group title.
2
Select any Set Up group
SET UP
Successive presses of the SET UP key will
sequentially display the other Set Up group titles shown
in the prompt hierarchy in Figure 3-1.
You can also use the [
] [ ] keys to scan the Set Up
groups in both directions.
Stop at the Set Up group title which describes the group
of parameters you want to configure. Then proceed to
the next step.
3
Select a Function Parameter
FUNCTION
LOOP 1/2
Upper Display
1.0
Shows you the current value or selection
for the first function prompt of the
particular Set Up group that you have
selected.
Lower Display
GAIN
Shows the first Function prompt within
that Set Up group.
Example displays show Set Up group Tuning, Function
prompt “Gain”, and the value selected.