112 UDC 3300 Process Controller Product Manual 4/00
4.8 Input 1 Parameters Set Up Group
Introduction
These are the parameters required for Input 1: actuation, transmitter
characterization, high and low range values in engineering units, ratio,
bias, filter, burnout, and emissivity.
Input 1 group prompts
Table 4-7 lists all the function prompts in the Input 1 Set Up group and
their definitions.
Table 4-7 Input 1 Group Definitions
Lower Display
Prompt
Upper Display
Range of Setting
or Selection
Parameter
Definition
IN1 TYPE
ATTENTION
Changing the input type
will result in the loss of
Field Calibration values
and will restore Factory
Calibration values.
DISABL
B TC
E TC H
E TC L
J TC H
J TC L
K TC H
K TC L
NNM H
NNM L
NM90 H
NM90 L
NIC TC
R TC
S TC
T TC H
T TC L
W TC H
W TC L
100 PT
100 LO
200 PT
500 PT
RAD RH
RAD RI
0-20mA
4-20mA
0-10mV
0-50mV
0-5 V
1-5 V
0-10 V
CARBON
OXYGEN
INPUT 1 ACTUATION TYPE – This selection determines
what actuation you are going to use for Input 1.
DISABLE—Disables Input.
B TC—B Thermocouple
E TC H—E Thermocouple High
E TC L—E Thermocouple Low
J TC H—J Thermocouple High
J TC L—J Thermocouple Low
K TC H—K Thermocouple High
K TC L—K Thermocouple Low
NNM H—Ni-Ni-Moly Thermocouple High
NNM L—Ni-Ni-Moly Thermocouple Low
NM90 H—NiMo-NiCo Thermocouple High
NM90 L—NiMo-NiCo Thermocouple Low
NIC TC—Nicrosil-Nisil Thermocouple
R TC—R Thermocouple
S TC—S Thermocouple
T TC H—T Thermocouple High
T TC L—T Thermocouple Low
W TC H—W5W26 Thermocouple High
W TC L—W5W26 Thermocouple Low
100 PT—100 Ohm RTD High
100 LO—100 Ohm RTD Low
200 PT—200 Ohm RTD
500 PT—500 Ohm RTD
RAD RH—Radiamatic RH
RAD RI—Radiamatic RI
0-20mA—0 to 20 Milliamperes
4-20mA—4 to 20 Milliamperes
0-10mV—0 to 10 Millivolts
0-50mV—0 to 50 Millivolts
0-5 V—0 to 5 Volts
1-5 V—1 to 5 Volts
0-10 V—0 to 10 Volts
Carbon
Oxygen