4.8 Input 1 Parameters Set Up Group
Introduction
These are the parameters required for Input 1: actuation, transmitter
characterization, high and low range values in engineering units, ratio,
bias, filter, burnout, and emissivity.
Input 1 group prompts
Table 4-7 lists all the function prompts in the Input 1 Set Up group and
their definitions.
Table 4-7 Input 1 Group Definitions
Lower Display
Prompt
Upper Display
Range of Setting
or Selection
Parameter
Definition
IN1 TYPE
ATTENTION
Changing the input type
will result in the loss of
Field Calibration values
and will restore Factory
Calibration values.
DISABL
B TC
E TC H
E TC L
J TC H
J TC L
K TC H
K TC L
NNM H
NNM L
NM90 H
NM90 L
NIC TC
R TC
S TC
T TC H
T TC L
W TC H
W TC L
100 PT
100 LO
200 PT
500 PT
RAD RH
RAD RI
0-20mA
4-20mA
0-10mV
0-50mV
0-5 V
1-5 V
0-10 V
CARBON
OXYGEN
INPUT 1 ACTUATION TYPE This selection determines
what actuation you are going to use for Input 1.
DISABLEDisables Input.
B TCB Thermocouple
E TC HE Thermocouple High
E TC LE Thermocouple Low
J TC HJ Thermocouple High
J TC LJ Thermocouple Low
K TC HK Thermocouple High
K TC LK Thermocouple Low
NNM HNi-Ni-Moly Thermocouple High
NNM LNi-Ni-Moly Thermocouple Low
NM90 HNiMo-NiCo Thermocouple High
NM90 LNiMo-NiCo Thermocouple Low
NIC TCNicrosil-Nisil Thermocouple
R TCR Thermocouple
S TCS Thermocouple
T TC HT Thermocouple High
T TC LT Thermocouple Low
W TC HW5W26 Thermocouple High
W TC LW5W26 Thermocouple Low
100 PT100 Ohm RTD High
100 LO100 Ohm RTD Low
200 PT200 Ohm RTD
500 PT500 Ohm RTD
RAD RHRadiamatic RH
RAD RIRadiamatic RI
0-20mA0 to 20 Milliamperes
4-20mA4 to 20 Milliamperes
0-10mV0 to 10 Millivolts
0-50mV0 to 50 Millivolts
0-5 V0 to 5 Volts
1-5 V1 to 5 Volts
0-10 V0 to 10 Volts
Carbon
Oxygen