3.11 Output Algorithm Parameters Set Up Group
Introduction
This data deals with various Output types that are available for use in the
controller. It also lists the Digital Output Status, the Current Duplex
functionality, and Relay Time Cycle increments.
Function prompts
Table 3-8 lists all the function prompts in the Output Algorithm Set Up
group.
Table 3-8 Output Algorithm Group Function Prompts
Function Prompt
Lower Display
Function
Name
Selections or
Range of Setting
Upper Display
Factory
Setting
Refer
to
OUT ALG
Loop 1 Output Algorithm TIME Time Simplex
CURRNT Current Simplex
POSITN Position Proportional
TIME D Time Duplex
CUR D Current Duplex
CUR TI Current/Time Duplex
TI CUR Time/Current Duplex
CURRNT
Section
4.7
4–20 RNG
Current Duplex Range 100PCT
50 PCT
100PCT
OUT2 ALG*
Loop 2 Output Algorithm NONE
TIME
CURRNT
CUR D
CUR TI
TI CUR
CURRNT
RLYSTATE
Digital Output State at 0 %
Output
1OF2OF (Output relays 1 and 2 are
both de-energized)
1ON2OF (Output relay 1 is
energized, output relay 2
is de-energized)
1OF2ON (Output relay 1 is de-
energized, output relay 2
is energized)
1ON2ON (Output relays 1 and 2 are
both energized)
1OF2ON
RLY TYPE
Relay Cycle Time Increments MECHAN (Cycle time in one second
increments)
SOL ST (Cycle time in 1/3 second
increments: 1 = .33
seconds, 120 = 40
seconds)
MECHAN
*Not available on DC330B