Honeywell UDC 3300 Universal Remote User Manual


 
4/00 UDC 3300 Controller Product Manual 149
Check the displays and
keys
Use the procedure in Table 5-2 to run the display and key test.
Table 5-2 Procedure for Testing the Displays and Keys
Press Result
SET UP
and hold in,
then
FUNCTION
LOOP 1/2
at the same time
The controller will run a display test. All the displays will
light for 8 seconds, then the displays will look like this:
try all
Lower Display
keys
Upper Display
Press each key to see if it
works
When the key is pressed, the lower display will indicate the
name of the key pressed.
Key Pressed Lower Display
FUNCTION LOOP 1/2 FUNCTION
LOWER DISPLAY LWR DISP
MANUAL/AUTO AUTO MAN
SETPOINT/SELECT SP SEL
INCRMENT
DECRMENT
RUN/HOLD RUN HOLD
+ INCRDECR
FUNCTION+SETUP FUNC SU
If no key is pressed for 20 seconds, the test will time out and the controller
will go into control mode.
If any test fails, go to Controller Failure Symptoms in Section 9 -
Troubleshooting.
Key error
When a key is pressed and the prompt KEY ERROR appears in the
lower display, it will be for one of the following reasons:
parameter is not available,
not in Set Up mode, press SET UP key first,
key malfunction, do keyboard test.