Step Operation Press Action/Result
FUNCTION
LOOP 1/2
until the lower display rolls through the rest
of the functions and returns to
Upper Display
Lower Display
IN nTYPE
New Selection
n = 1, 2, or 3
or
until you change the input selection in the
upper display back to the proper selection.
You will see:
Upper Display
Lower Display
Original input
selection that
matches your
type of sensor.
IN nTYPE
n = 1, 2, or 3
3
Return to
normal
operating mode
LOWER
DISPLAY
to return to Normal operating mode.
The factory calibration will be restored. If the
problem is not corrected, contact the
Honeywell Technical Assistance Center.
1-800-423-9883 USA and Canada
CAUTION
A restored factory calibration overwrites any previous field calibration
done for the input and may change the High and Low Range Limits. Be
sure to protect any field calibration from accidental overwrites by
configuring the appropriate LOCKOUT selection after calibration. See the
Section 3 - Configuration for specific instructions to set the lockout.