4/00 UDC 3300 Process Controller Product Manual 59
Function Prompt
Lower Display
Function
Name
Selections or
Range of Setting
Upper Display
Factory
Setting
Refer
to
OUT RATE
ATTENTION
Does not apply to 3
Position Step
Control algorithm.
Output Change Rate ENABLE
DISABL
DISABL
Section
4.11
PCT/M UP
Output Rate Up Value 0 to 9999 % per minute 0
PCT/M DN
Output Rate Down Value 0 to 9999 % per minute 0
OUTHiLIM
High Output Limit –5.0 to 105 % of output 100
OUTLoLIM
Low Output Limit –5.0 to 105 % of output 0.0
I Hi LIM
High Reset Limit Within the range of the output limits 100.0
I Lo LIM
Low Reset Limit Within the range of the output limits 0.0
DROPOFF
Controller Dropoff Value –5 to 105 % of output 0
DEADBAND
Output Relay Deadband Time Duplex:
–5.0 to 25.0 %
On/Off Duplex:
0.0 to 25.0 %
Position Prop. and 3P Step:
0.5 to 5.0 %
1.0
OUT HYST
Output Relay Hysteresis 0.0 to 100.0 % of PV Span for On/Off
control.
0.5
FAILMODE
Failsafe Mode NO LAT
LATCH
NO LAT
FAILSAFE
Failsafe Output Value for all
outputs except 3P Step
Set within the range of the output
limits. 0 to 100 %
0.0
Failsafe Output Value for 3P
Step
0 PCT (motor goes to closed position)
100PCT (motor goes to open position)
- -
SW_FAIL
PDMR/Position Proportional
motor position when
slidewire fails
0 PCT (motor goes to closed position)
100PCT (motor goes to open position)
MAN OUT
Power-up Preset Output for
Manual Output
Within the range of output limits - -
AUTO OUT
Power-up Preset Output for
Automatic Output
Within the range of output limits - -
PBorGAIN
Proportional Band or
Gain Units
PB PCT
GAIN
GAIN
MINorRPM
Reset Units RPM
MIN
MIN