Honeywell UDC 3300 Universal Remote User Manual


 
4/00 UDC 3300 Controller Product Manual 259
Procedure #7
Table 9-14 explains how to troubleshoot a Keyboard failure.
Table 9-14 Troubleshooting a Keyboard Failure
Step What to do How to do it
1
Make sure the keyboard is
connected properly to the
MCU/output and power/input
boards.
Withdraw the chassis from the case
and visually inspect the connection.
2
Controller Keyboard or specific keys
may be LOCKED OUT via the
security code.
Use your four-digit security code
number to change the lockout level.
Refer to Section 3 Configuration.
ATTENTION
Using 1000 as a
security code number will override the
4-digit code previously entered.
3
Run the keyboard test. Press the [SET UP] key and hold in,
then press the [FUNCTION] key at the
same time. The controller will run a
display test. Then you will see:
TRY ALL
Lower Display
KEYS
Upper Display
Press each key. If it works, the key
name will appear in the lower display.
4
Replace the display/keyboard if any
keys are shorted out.
Refer to Parts Replacement
Procedures in this section.