4/00 UDC 3300 Controller Product Manual 215
Function Press Result
External Program
Reset
To Begin
If Remote Switching (Digital Input option) is
present on your controller, contact closure
resets the SP Program back to the start of
the first segment.
Program cycle number is not affected.
Reopening the contact has no effect and
places the program in HOLD mode.
The setpoint is changed to what the setpoint
was when the program was first started.
RUN
HOLD
restarts the Setpoint Program
Keyboard Reset
LOWER
DISPLAY
until you see
Upper Display
Lower Display
ToBEGIN
Press [] key to reset program to beginning
at Hold state.
Viewing the present
ramp or soak
segment number
and time
LOWER
DISPLAY
until you see
Upper Display
R and the PV value
Lower Display
For Ramp segments:
# RA XX.XX
Segment Number (odd only)
Indicates Ramp segment
Ramp Time - Hours.Minutes or
Ramp Rate - EU/MIN or EU/HR
For Soak segments:
# SK XX.XX
Segment Number (even only)
Indicates Soak segment
Time remaining in segment in
Hrs.Minutes including current
partially completed minute