44 UDC 3300 Process Controller Product Manual 4/00
3.7 Loop 2 Tuning Parameters Set Up Group (Cascade or
Two Loops
Function prompts
Table 3-4 lists all the function prompts in the Tuning 2 Set Up group. This
group is only displayed if the controller is configured for Cascade or
2-Loop control (prompt PIDLOOPS in Algorithm Data Set Up group).
Table 3-4 Tuning Loop 2 Group Function
Function Prompt
Lower Display
Function
Name
Selections or
Range of Setting
Upper Display
Factory
Setting
Refer
to
PROPBD3
or
GAIN 3
Proportional Band 3
or
Gain 3
0.1 to 9999
0.001 to 1000
- -
1.000
Section
4.3
or
GAINVALn
or
Gain Value being used by
Gain Scheduling when
enabled
Read Only - -
RATE3MIN
Rate 3 in Minutes 0.00 to 10.00 minutes 0.00
RSET3MIN
or
RSET3RPM
Reset 3 in minutes/repeat
or
Reset 3 in repeats/minute
0.02 to 50.00 1.00
- -
MANRSET3
Manual Reset 3 100 to 100 % Output 0.0
PROPBD4
or
GAIN 4
Proportional Band 4
or
Gain 4
0.1 to 9999 %
0.001 to 1000
- -
1.000
RATE4MIN
Rate 4 in Minutes 0.00 to 10.00 minutes 0.00
RSET4MIN
or
RSET4RPM
Reset 4 in minutes/repeat
or
Reset 4 in repeats/minute
0.02 to 50.00 1.00
- -
CYC3 SEC*
or
CYC3 SX3*
Cycle Time 3 (Heat) 1 to 120 20
CYC4 SEC*
or
CYC4 SX3*
Cycle Time 4 (Cool) 1 to 120 20
PVEUVAL1
PVEUVAL2
PVEUVAL3
PVEUVAL4
PVEUVAL5
PVEUVAL6
PVEUVAL7
PVEUVAL8
PV1 (through PV8) Value for
Gain Scheduling
PV value within the PV limits.
In engineering units
0
GAINVAL1**
GAINVAL2**
GAINVAL3**
GAINVAL4**
GAINVAL5**
GAINVAL6**
GAINVAL7**
GAINVAL8**
Gain 1 (through Gain 8)
Value for Gain Scheduling
0.001 to 1000 floating
Gain or Proportional Band
1.000
*Cycle times are in either 1 second or 1/3 second increments, depending upon the RLY TYPE configuration in the
Output Algorithm Set Up group.
** ATTENTION
If units of percent proportional band (PB) are selected under the Control Set Up prompt, function
prompt PBorGAIN, then the displayed values are in %PB, but the lower display will still show Gain.