42 UDC 3300 Process Controller Product Manual 4/00
3.6 Loop 1 Tuning Parameters Set Up Group
Function prompts
Table 3-3 lists all the function prompts in the Tuning Set Up group. How
the Algorithm and Control Set Up groups are configured determines
which prompts will appear.
Table 3-3 Tuning Group Function Prompts
Function Prompt
Lower Display
Function
Name
Selections or
Range of Setting
Upper Display
Factory
Setting
Refer
to
PROP BD
or
GAIN
Proportional Band
or
Gain
0.1 to 9999 %
0.001 to 1000
- -
1.000
Section
4.2
or
GAINVALn***
or
Gain Value being used by
Gain Scheduling when
enabled in Control Setup
group PID SETS
Read Only - -
RATE MIN
Rate in Minutes 0.00 to 10.00 minutes 0.00
RSET MIN
or
RSET RPM
Reset in minutes/repeat
or
Reset in repeats/minute
0.02 to 50.00 1.00
- -
MAN RSET
Manual Reset 100 to 100 % output 0
PROPBD2
or
GAIN 2
Proportional Band 2
or
Gain 2
0.1 to 9999 %
0.001 to 1000
- -
1.000
RATE2MIN
Rate 2 in Minutes 0.00 to 10.00 minutes 0.00
RSET2MIN
or
RSET2RPM
Reset 2 in minutes/repeat
or
Reset 2 in repeats/minute
0.02 to 50.00 1.00
- -
CYC SEC*
or
CYC SX3*
Cycle Time (Heat) 1 to 120 20
CYC2 SEC*
or
CYC2 SX3*
Cycle Time (Cool) 1 to 120 20
SECURITY
Security Code 0 to 4095 0
LOCKOUT
Configuration Lockout NONE
CALIB
+ CONF
+ VIEW
MAX
CALIB
AUTO MAN**
Manual/Auto Key Lockout DISABL
ENABLE
ENABLE
SP SEL**
Setpoint Select Key Lockout DISABL
ENABLE
ENABLE
*Cycle times are in either 1 second or 1/3 second increments, depending upon the RLY TYPE configuration in the
Output Algorithm Set Up group.
**Only appears if LOCKOUT = NONE.
***Requires Math software option