4/00 UDC 3300 Process Controller Product Manual 51
Function Prompt
Lower Display
Function
Name
Selections or
Range of Setting
Upper Display
Factory
Setting
Refer
to
CALC HI
Calculated Variable High
Scaling Factor for Input
Algorithm 2
999. To 9999. Floating
(in engineering units)
- -
CALC LO
Calculated Variable Low
Scaling Factor for Input
Algorithm 2
999. To 9999. Floating
(in engineering units)
- -
ALG2 INA
Input Algorithm 2
Input A Selection
INP 1 IN AL1
INP 2 IN AL2
LP1OUT INP 3
LP2OUT
- -
ALG2 INB
Input Algorithm 2
Input B Selection
INP 1 IN AL1
INP 2 IN AL2
LP1OUT INP 3
LP2OUT
- -
ALG2 INC
Input Algorithm 2
Input C Selection
NONE LP2OUT
INP 1 IN AL1
INP 2 IN AL2
LP1OUT INP 3
- -
PCT H2
Hydrogen Content for
Dewpoint
1.0 to 99.0 % 1.0
ALG2 BIAS
Input Algorithm2 Bias -999 to 9999 floating (in engineering
units)
0.000
8SEG CH1*
Eight Segment Characterizer
If Characterizer 1 is
enabled, the following Xn
VALUE and Yn VALUE
parameters appear.
DISABL
INPUT1
INPUT2
L1 OUT
L2 OUT
DISABL
X0 VALUE
X1 VALUE
X2 VALUE
X3 VALUE
X4 VALUE
X5 VALUE
X6 VALUE
X7 VALUE
X8 VALUE
Xn Input Value (X Axis)
(n = 0 through 8)
0 to 99.99 % 0
Y0 VALUE
Y1VALUE
Y2VALUE
Y3VALUE
Y4VALUE
Y5VALUE
Y6VALUE
Y7VALUE
Y8 VALUE
Yn Output Value (Y Axis)
(n = 0 through 8)
0 to 99.99 % 0
8SEG CH2*
Eight Segment Characterizer
2
If Characterizer 2 is
enabled, the following Xn
VALU2 and Yn VALU2
parameters appear.
DISABL
INPUT1
INPUT2
L1 OUT
L2 OUT
DISABL