4/00 UDC 3300 Process Controller Product Manual 57
3.14 Input 3 Parameters Set Up Group
Introduction
This data deals with various parameters required to configure Input 3.
Function prompts
Table 3-11 lists all the function prompts in the Input 3 Set Up group.
Table 3-11 Input 3 Group Function
Function Prompt
Lower Display
Function
Name
Selections or
Range of Setting
Upper Display
Factory
Setting
Refer
to
IN3 TYPE*
Input 3 Actuation Type DISABL
0-20mA
4-20mA
0-5 V
1-5 V
DISABL
Section
4.10
XMITTER3
Transmitter Characterization B TC S TC
E TC H T TC H
E TC L T TC L
J TC H W TC H
J TC L W TC L
K TC H 100 PT
K TC L 100 LO
NNM H 200 PT
NNM L 500 PT
NM90 H RAD RH
NM90 L RAD RI
NIC TC LINEAR
R TC SQROOT
LINEAR
IN3 HI
Input 3 High Range Value
(Linear Inputs only)
999. to 9999. floating
(in engineering units)
1000
IN3 LO
Input 3 Low Range Value
(Linear Inputs only)
999. to 9999. floating
(in engineering units)
0
RATIO 3
Input 3 Ratio 20.00 to 20.00 1.000
BIAS IN3
Input 3 Bias 999. to 9999.
(in engineering units)
0
FILTER 3
Input 3 Filter 0 to 120 seconds 0
*Not available on DC330B