222 UDC 3300 Process Controller Product Manual 4/00
Equipment needed
Table 7-2 lists the equipment you will need to calibrate the specific types
of inputs that are listed in the table. You will need a screwdriver to
connect these devices to your controller.
Table 7-2 Equipment Needed
Type of Input Equipment Needed
Thermocouple Inputs
(Ice Bath)
A calibrating device with ± 0.02 % accuracy for use
as a signal source such as a millivolt source.
Thermocouple extension wire that corresponds with
the type of thermocouple that will be used with the
controller input.
Two insulated copper leads for connecting the
thermocouple extension wire from the ice baths to
the precision calibrator.
Two containers of crushed ice.
Thermocouple Inputs
(Precision Resistor)
A calibrating device with ± 0.02 % accuracy for use
as a signal source such as a millivolt source.
Two insulated copper leads for connecting the
calibrator to the controller.
A precision 500 ohm resistor ± 0.1 % connected
across input #1 terminals 25 (R) and 27 () or input
#2 terminals 22 (R) and 24 ().
RTD (Resistance Thermometer
Device)
A decade box, with ± 0.02 % accuracy, capable of
providing stepped resistance values over a
minimum range of 0 to 1400 ohms with a resolution
of 0.1 ohm.
Three insulated copper leads for connecting the
decade box to the controller.
Milliampere, Millivolt, Volts, and
Radiamatic
A calibrating device with ± 0.02 % accuracy for use
as a signal source.
Two insulated copper leads for connecting the
calibrator to the controller.
Place current source at zero before switching ON.
Do not switch current sources OFF/ON while
connected to the UDC 3300 input.