4/00 UDC 3300 Controller Product Manual 177
5.13 Configuring Two Loops of Control
Select 2-loop algorithm
The procedure in Table 5-24 shows you how select the 2-loop algorithm.
Table 5-24 Procedure for Selecting 2-loop Algorithm
Step Operation Press Action
1
Select Algorithm
Set Up Group
SET UP
until you see:
ALGORTHM
Lower Display
SET UP
Upper Display
2
Select the PID
Loops
FUNCTION
LOOP 1/2
to successively display the following
constants:
ALGORTHM
Lower Display
Upper Display
1 LOOP
2LOOPS
CASCAD
or
To select two Loops or Cascade control.
Select the output
algorithm for each loop
See Section 5.12 for rules and regulations, then follow the procedure in
Table 5-25.
Table 5-25 Procedure for Selecting Output Algorithm
Step Operation Press Action
1
Select Output
Algorithm Set Up
Group
SET UP
until you see:
OUT ALG
Lower Display
SET UP
Upper Display
2
Select Loop 1
Algorithms
FUNCTION
LOOP 1/2
to successively display the following
constants:
OUT ALG
Lower Display
Upper Display
TIME
CURRNT
POSITN
TIME D
CUR D
CUR TI
TI CUR
or
to select Loop 1 algorithm.