6-44 Programming MN792
Stop Rates Continued
Functional Description
Stop Hierarchy
Coast Stop Terminal B9
Disables the drive and opens the contactor using the pilot output
Enable Terminal C4
Suspends and resets the control loops
Program Stop Terminal B8
Independent ramp time
Stop Timer
Independent current limit may be greater than normal current limit
Independent zero speed
Normal Run/Stop Terminal C3
Independent ramp time
Contactor Delay
Note: The Controls reaction to commands is defined by a state machine. This determines which commands
provide the demanded action, and in which sequence. Consequently, Coast Stop and Program Stop
must be false (the Control is not in Coast or Program mode), before a Run signal is applied. Otherwise
the control assumes a stop mode and remains disabled.
Normal Stop Sequence
Stop Zero Speed settings less than 0.25% allow the control to remain enabled for the Contactor Delay Time
after reaching Stop Zero Speed. This is useful for Jog applications.
0
100
Speed Setpoint %
0
100
Speed Demand %
0
100
Speed Feedback %
0
Drive Enable
2
Stop Zero Speed 2.00%
Stop Time
10.0 Seconds
Actual stop rate depends on load inertia, motor horse power and
overload capacity of drive (motor + control)
Enabled
Disabled
Control is disabled below
Stop Zero Speed if set>0.25%
Control remains enabled for the Contactor Delay if
Stop Zero Speed <0.25%
Start / Run (C3)