B-10 Parameter Table MN792
Parameter Values Continued R/W: RO = Read Only, RW = Read / Write
Table B-2 Parameters Listed by Name
Tag R/W Name Keypad Menu WB Block Range Factory Setting MN Notes
266 RW % S-RAMP SETUP PARAMETERS::RAMPS Ramps 0.00 to 100.00 % 2.50% he
245 RW % TO GET 10V SYSTEM::CONFIGURE I/O::ANALOG OUTĆ
PUTS::ANOUT 1 (A7)
Analog Output 1 -300.00 to 300.00 % 100.00% gt
248 RW % TO GET 10V SYSTEM::CONFIGURE I/O::ANALOG OUTĆ
PUTS::ANOUT 2 (A8)
Analog Output 2 -300.00 to 300.00 % 100.00% gw
111 RW 5703 RCV ERROR SETUP PARAMETERS::INHIBIT ALARMS Alarms 0 : Enabled 1 : Inhibited Enabled d3
61 RO ACTUAL NEG I LIM DIAGNOSTICS Diagnostics xxx.xx % (h) -90.0% bp Output
67 RO ACTUAL POS I LIM DIAGNOSTICS Diagnostics xxx.xx % (h) 90.00% bv Output
30 RW Additional DEM SETUP PARAMETERS::CURRENT LOOP Current Loop -200.00 to 200.00 % 0.00% au
204 RW Aiming Point SETUP PARAMETERS::INVERSE TIME Inverse Time 0.00 to 103.00 % 103.00% fo 2, 4
23 RW Analog TACH CAL SETUP PARAMETERS::CALIBRATION Calibration 0.9800 to 1.1000 1.0000 an
50 RO ANIN 1 (A2) DIAGNOSTICS Analog Input 1 xxx.xx VOLTS 0.00V be Output
51 RO ANIN 2 (A3) DIAGNOSTICS Analog Input 2 xxx.xx VOLTS 0.00V bf Output
52 RO ANIN 3 (A4) DIAGNOSTICS Analog Input 3 xxx.xx VOLTS 0.00V bg Output
53 RO ANIN 4 (A5) DIAGNOSTICS Analog Input 4 xxx.xx VOLTS 0.00V bh Output
54 RO ANIN 5 (A6) DIAGNOSTICS Analog Input 5 xxx.xx VOLTS 10.00V bi Output
128 RW ANOUT 1 SETUP PARAMETERS::AUX I/O Aux I/O -100.00 to 100.00 % 0.00% dk
55 RO ANOUT 1 (A7) DIAGNOSTICS Analog Output 1 xxx.xx VOLTS (h) 0.00V bj Output
129 RW ANOUT 2 SETUP PARAMETERS::AUX I/O Aux I/O -100.00 to 100.00 % 0.00% dl
56 RO ANOUT 2 (A8) DIAGNOSTICS Analog Output 2 xxx.xx VOLTS (h) 0.00V bk Output
605 RO ARM Volts FBK DIAGNOSTICS Unallocated 0 Volts Output
523 RW Armature Current CONFIGURE DRIVE Calibration 2.0 to 15.0 AMPS 2.0 Amps oj 3
25 RW Armature I (A9) SETUP PARAMETERS::CALIBRATION Calibration 0 : UNIPOLAR
1 : BIPOLAR
Bipolar ap
20 RW Armature V CAL. SETUP PARAMETERS::CALIBRATION Calibration 0.9800 to 1.1000 1.0000 ak
42 RO At Current Limit DIAGNOSTICS Current Loop 0 : False 1 : True False b6 Output
79 RO At Standstill DIAGNOSTICS Standstill 0 : False 1 : True True c7 Output
78 RO At Zero Setpoint DIAGNOSTICS Standstill 0 : False 1 : True True c6 Output
77 RO At Zero Speed DIAGNOSTICS Standstill 0 : False 1 : True True c5 Output
287 RW Auto Reset SETUP PARAMETERS::RAMPS Ramps 0 : Disabled 1 : Enabled Enabled hz
18 RO Autotune CONFIGURE DRIVE Current Loop 0 : Off 1 : On Off ai Output, 1
94 RW AUX DIGOUT 1 SETUP PARAMETERS::AUX I/O Aux I/O 0 : Off 1 : On Off cm
95 RW AUX DIGOUT 2 SETUP PARAMETERS::AUX I/O Aux I/O 0 : Off 1 : On Off cn
96 RW AUX DIGOUT 3 SETUP PARAMETERS::AUX I/O Aux I/O 0 : Off 1 : On Off co
168 RW Aux Enable SETUP PARAMETERS::AUX I/O Aux I/O 0 : Off 1 : On On eo
227 RW AUX JOG SETUP PARAMETERS::AUX I/O Aux I/O 0 : Off 1 : On On gb
161 RW AUX START SETUP PARAMETERS::AUX I/O Aux I/O 0 : Off 1 : On On eh
60 RO BACK EMF DIAGNOSTICS Calibration xxx.xx % (h) 0.0% bo Output
192 RW BEMF FBK LAG SETUP PARAMETERS::FIELD CONĆ
TROL::FLD.CURRENT VARS::FLD.WEAK VARS
Field Control 10 to 5000 100 fc
191 RW BEMF FBK LEAD SETUP PARAMETERS::FIELD CONĆ
TROL::FLD.CURRENT VARS::FLD.WEAK VARS
Field Control 10 to 5000 100 fb
90 RW Bipolar Clamps SETUP PARAMETERS::CURRENT LOOP Current Loop 0 : Disabled 1 : Enabled Disabled ci
230 RW Calibration SYSTEM::CONFIGURE I/O::ANALOG INĆ
PUTS::ANIN 1 (A2)
Analog Input 1 -3.0000 to 3.0000 1.0000 ge
233 RW Calibration SYSTEM::CONFIGURE I/O::ANALOG INĆ
PUTS::ANIN 2 (A3)
Analog Input 2 -3.0000 to 3.0000 1.0000 gh
236 RW Calibration SYSTEM::CONFIGURE I/O::ANALOG INĆ
PUTS::ANIN 3 (A4)
Analog Input 3 -3.0000 to 3.0000 1.0000 gk
239 RW Calibration SYSTEM::CONFIGURE I/O::ANALOG INĆ
PUTS::ANIN 4 (A5)
Analog Input 4 -3.0000 to 3.0000 1.0000 gn
242 RW Calibration SYSTEM::CONFIGURE I/O::ANALOG INĆ
PUTS::ANIN 5 (A6)
Analog Input 5 -3.0000 to 3.0000 1.0000 gq
121 RW Change Password PASSWORD 0x0000 to 0xFFFF 0x0000 dd
525 RO Coast Stop DIAGNOSTICS Stop Rates 0 : False 1 : True FALSE ol Output
39 RW Configure Enable CONFIGURE DRIVE Unallocated 0 : Disabled 1 : Enabled Disabled b3 2
4 RW Constant Accel SETUP PARAMETERS::RAMPS Ramps 0 : Disabled 1 : Enabled Enabled a4
83 RO Contactor Closed DIAGNOSTICS Unallocated 0 : Off 1 : On Off cb Output
302 RW Contactor Delay SETUP PARAMETERS::STOP RATES Stop Rates 0.1 to 600.0 Secs 1.0 Secs ie
225 RW Crawl Speed SETUP PARAMETERS::JOG/SLACK Jog/Slack -100.00 to 100.00 % 10.00% g9