Baldor mn792 Universal Remote User Manual


 
B-24 Parameter Table MN792
Table B-3 Parameters Listed by Keypad Menu Continued
Tag R/W Name Keypad Menu WB Block Range Factory Setting MN Notes
309 RW Input 0 SETUP PARAMETERS::SETPOINT SUM 1 Setpoint Sum 1 -200.00 to 200.00 % 0.00% il
100 RW Input 1 SETUP PARAMETERS::SETPOINT SUM 1 Setpoint Sum 1 -200.00 to 200.00 % 0.00% cs
423 RW Input 2 SETUP PARAMETERS::SETPOINT SUM 1 Setpoint Sum 1 -200.00 to 200.00 % 0.00% lr
375 RW Limit SETUP PARAMETERS::SETPOINT SUM 1 Setpoint Sum 1 0.00 to 200.00 % 105.00% kf
208 RW Ratio 0 SETUP PARAMETERS::SETPOINT SUM 1 Setpoint Sum 1 -3.0000 to 3.0000 1.0000 fs
6 RW Ratio 1 SETUP PARAMETERS::SETPOINT SUM 1 Setpoint Sum 1 -3.0000 to 3.0000 1.0000 a6
292 RW SIGN 0 SETUP PARAMETERS::SETPOINT SUM 1 Setpoint Sum 1 0 : Negative 1 : Positive Positive i4
8 RW Sign 1 SETUP PARAMETERS::SETPOINT SUM 1 Setpoint Sum 1 0 : Negative 1 : Positive Positive a8
401 RW DERIVATIVE TC SETUP PARAMETERS::SPECIAL BLOCKS::PID PID 0.000 to 10.000 Secs 0.000Secs l5
418 RW Divider 1 SETUP PARAMETERS::SPECIAL BLOCKS::PID PID -3.0000 to 3.0000 1.0000 lm
414 RW Divider 2 SETUP PARAMETERS::SPECIAL BLOCKS::PID PID -3.0000 to 3.0000 1.0000 li
408 RW Enable SETUP PARAMETERS::SPECIAL BLOCKS::PID PID 0 : Disabled 1 : Enabled Enabled lc
403 RW FILTER T.C. SETUP PARAMETERS::SPECIAL BLOCKS::PID PID 0.000 to 10.000 Secs 0.100 Secs l7
410 RW Input 1 SETUP PARAMETERS::SPECIAL BLOCKS::PID PID -300.00 to 300.00 % 0.00% le
411 RW Input 2 SETUP PARAMETERS::SPECIAL BLOCKS::PID PID -300.00 to 300.00 % 0.00% lf
409 RW INT. DEFEAT SETUP PARAMETERS::SPECIAL BLOCKS::PID PID 0 : Off 1 : On Off ld
402 RW INT.TIME.CONST SETUP PARAMETERS::SPECIAL BLOCKS::PID PID 0.01 to 100.00 Secs 5.00 Secs l6
474 RW MIN PROFILE GAIN SETUP PARAMETERS::SPECIAL BLOCKS::PID PID 0.00 to 100.00 % 20.00% n6
473 RW Mode SETUP PARAMETERS::SPECIAL BLOCKS::PID PID 0 to 4 0 n5
406 RW Negative Limit SETUP PARAMETERS::SPECIAL BLOCKS::PID PID -105.00 to 0.00 % -100.00% la
407 RW O/P SCALER(TRIM) SETUP PARAMETERS::SPECIAL BLOCKS::PID PID -3.0000 to 3.0000 0.2000 lb
405 RW Positive Limit SETUP PARAMETERS::SPECIAL BLOCKS::PID PID 0.00 to 105.00 % 100.00% l9
475 RO Profiled Gain SETUP PARAMETERS::SPECIAL BLOCKS::PID PID xxxx.x 0.0 n7 Output
404 RW PROP. GAIN SETUP PARAMETERS::SPECIAL BLOCKS::PID PID 0.0 to 100.0 1.0 l8
412 RW Ratio 1 SETUP PARAMETERS::SPECIAL BLOCKS::PID PID -3.0000 to 3.0000 1.0000 lg
413 RW Ratio 2 SETUP PARAMETERS::SPECIAL BLOCKS::PID PID -3.0000 to 3.0000 1.0000 lh
202 RW INT. DEFEAT SETUP PARAMETERS::SPEED LOOP Speed Loop 0 : Off 1 : On Off fm
547 RW SPD.FBK.FILTER SETUP PARAMETERS::SPEED LOOP Menus 0.000 to 1.000 0.000 p7
274 RW I GAIN IN RAMP SETUP PARAMETERS::SPEED LOOP::ADĆ
VANCED
Advanced 0.0000 to 2.0000 1.0000 hm
273 RW POS. LOOP P GAIN SETUP PARAMETERS::SPEED LOOP::ADĆ
VANCED
Advanced -200.00 to 200.00 % 0.00% hl 4
268 RW Mode SETUP PARAMETERS::SPEED LOOP::ADĆ
VANCED::ADAPTION
Advanced 0 to 3 0 hg
271 RW PROP. GAIN SETUP PARAMETERS::SPEED LOOP::ADĆ
VANCED::ADAPTION
Advanced 0.00 to 200.00 5.00 hj
269 RW SPD BRK1 (LOW) SETUP PARAMETERS::SPEED LOOP::ADĆ
VANCED::ADAPTION
Advanced 0.00 to 100.00 % 1.00% hh
270 RW SPD BRK2 (HIGH) SETUP PARAMETERS::SPEED LOOP::ADĆ
VANCED::ADAPTION
Advanced 0.00 to 100.00 % 5.00% hi
272 RW SPD.INT.TIME SETUP PARAMETERS::SPEED LOOP::ADĆ
VANCED::ADAPTION
Advanced 0.001 to 30.000 Secs 0.500 Secs hk
285 RW ZERO IAD LEVEL SETUP PARAMETERS::SPEED LOOP::ADĆ
VANCED::ZERO SPD. QUENCH
Advanced 0.00 to 200.00 % 1.50% hx
284 RW ZERO SPD. LEVEL SETUP PARAMETERS::SPEED LOOP::ADĆ
VANCED::ZERO SPD. QUENCH
Advanced 0.00 to 200.00 % 0.50% hw
357 RW Max Demand SETUP PARAMETERS::SPEED LOOP::SETĆ
POINTS
Speed Loop 0.00 to 105.00 % 105.00% jx
358 RW Min Demand SETUP PARAMETERS::SPEED LOOP::SETĆ
POINTS
Speed Loop -105.00 to 105.00 % -105.00% jy
7 RW Ratio 2 (A3) SETUP PARAMETERS::SPEED LOOP::SETĆ
POINTS
Speed Loop -3.0000 to 3.0000 .0000 a7
289 RW Setpoint 1 SETUP PARAMETERS::SPEED LOOP::SETĆ
POINTS
Speed Loop -105.00 to 105.00 % 0.00% i1
290 RO Setpoint 2 (A3) SETUP PARAMETERS::SPEED LOOP::SETĆ
POINTS
Speed Loop xxx.xx % 0.00% i2 Output
291 RW Setpoint 3 SETUP PARAMETERS::SPEED LOOP::SETĆ
POINTS
Speed Loop -105.00 to 105.00 % 0.00% i3
41 RW Setpoint 4 SETUP PARAMETERS::SPEED LOOP::SETĆ
POINTS
Speed Loop -105.00 to 105.00 % 0.00% b5
9 RW Sign 2 (A3) SETUP PARAMETERS::SPEED LOOP::SETĆ
POINTS
Speed Loop 0 : Negative 1 : Positive Positive a9