Baldor mn792 Universal Remote User Manual


 
A-2 CE Guidelines MN792
Using CE approved components will not guarantee a CE compliant system!
1. The components used in the drive, installation methods used, materials selected for interconnection
of components are important.
2. The installation methods, interconnection materials, shielding, filtering and grounding of the system
as a whole will determine CE compliance.
3. The responsibility of CE mark compliance rests entirely with the party who offers the end system for
sale (such as an OEM or system integrator).
Baldor products which meet the EMC directive requirements are indicated with a “CE” mark. A duly signed CE
declaration of conformity is available from Baldor.
EMC Wiring Technique
1 CABINET
The drawing shows an electroplated zinc coated enclosure,
which is connected to ground.
This enclosure has the following advantages:
– All parts mounted on the back plane are connected to ground.
– All shield (screen) connections are connected to ground.
Within the cabinet there should be a spatial separation between
power wiring (motor and AC power cables) and control wiring.
2 SCREEN CONNECTIONS
All connections between components must use shielded cables.
The cable shields must be connected to the enclosure. Use
conductive clamps to ensure good ground connection. With this
technique, a good ground shield can be achieved.
3 EMC – FILTER
The EMI or main filter should be mounted next to the power
supply (here BPS). For the connection to and from the main
filter screened cables should be used. The cable screens should
be connected to screen clamps on both sides. (Exception:
Analog Command Signal).
4 Grounding (Earth)
For safety reasons (VDE0160), all BALDOR components must
be connected to ground with a separate wire. The diameter of
the wire must be at minimum AWG#6 (10mm@). Ground
connections (dashed lines) must be made from the central
ground to the regen resistor enclosure and from the central
ground to the Shared Power Supply.
5 Y–CAPACITOR
The connection of the regeneration resistor can cause RFI (radio
frequency interference) to be very high. To minimize RFI, a
Y–capacitor is used. The capacitor should only be connected
between the dynamic brake resistor housing and terminal pin R1
(lead from Lin).
Recommendation: 0,1µF / 250VAC Type: PME265
BALDOR–Ordering–No.: ASR27104
Y
Capacitor