B-28 Parameter Table MN792
Parameter Values Continued R/W: RO = Read Only, RW = Read / Write
Table B-4 Parameters Listed by WB Block
Tag R/W Name Keypad Menu WB Block Range Factory Setting MN Notes
543 RW Zero CAL Inputs CONFIGURE DRIVE Up To Action Requested p3 1, 2, 3, 4
121 RW Change Password PASSWORD 0x0000 to 0xFFFF 0x0000 dd
120 RW Enter Password PASSWORD 0x0000 to 0xFFFF 0x0000 dc 1
198 RW P3 Baud Rate SERIAL LINKS::SYSTEM PORT (P3)::P3 SETĆ
UP
0:300 1:600 2:1200
3:2400 4:4800 5:9600
6:19200
9600 fi 2
123 RW Peek Data SYSTEM::PEEK 0x0000 to 0xFFFF 0x0078 df
124 RW Peek Scale SYSTEM::PEEK -300.00 to 300.00 8.00 dg
187 RO Raw Input SERIAL LINKS::SYSTEM PORT (P3)::P3 SETĆ
UP::5703 SUPPORT
5703 xxx.xx % 0.00% f7 Output
189 RO Scaled Input SERIAL LINKS::SYSTEM PORT (P3)::P3 SETĆ
UP::5703 SUPPORT
5703 xxx.xx % 0.00% f9 Output, 2
132 RW SETPT. RATIO SERIAL LINKS::SYSTEM PORT (P3)::P3 SETĆ
UP::5703 SUPPORT
5703 -3.0000 to 3.0000 0.0000 do
133 RW SETPT. SIGN SERIAL LINKS::SYSTEM PORT (P3)::P3 SETĆ
UP::5703 SUPPORT
5703 0 : Negative 1 : Positive Positive dp
134 RW Source Tag SYSTEM::CONFIGURE I/O::CONFIGURE 5703 5703 0 to 549 89 dq 2, 3
274 RW I GAIN IN RAMP SETUP PARAMETERS::SPEED LOOP::ADĆ
VANCED
Advanced 0.0000 to 2.0000 1.0000 hm
273 RW POS. LOOP P GAIN SETUP PARAMETERS::SPEED LOOP::ADĆ
VANCED
Advanced -200.00 to 200.00 % 0.00% hl 4
268 RW Mode SETUP PARAMETERS::SPEED LOOP::ADĆ
VANCED::ADAPTION
Advanced 0 to 3 0 hg
271 RW PROP. GAIN SETUP PARAMETERS::SPEED LOOP::ADĆ
VANCED::ADAPTION
Advanced 0.00 to 200.00 5.00 hj
269 RW SPD BRK1 (LOW) SETUP PARAMETERS::SPEED LOOP::ADĆ
VANCED::ADAPTION
Advanced 0.00 to 100.00 % 1.00% hh
270 RW SPD BRK2 (HIGH) SETUP PARAMETERS::SPEED LOOP::ADĆ
VANCED::ADAPTION
Advanced 0.00 to 100.00 % 5.00% hi
272 RW SPD.INT.TIME SETUP PARAMETERS::SPEED LOOP::ADĆ
VANCED::ADAPTION
Advanced 0.001 to 30.000 Secs 0.500 Secs hk
285 RW ZERO IAD LEVEL SETUP PARAMETERS::SPEED LOOP::ADĆ
VANCED::ZERO SPD. QUENCH
Advanced 0.00 to 200.00 % 1.50% hx
284 RW ZERO SPD. LEVEL SETUP PARAMETERS::SPEED LOOP::ADĆ
VANCED::ZERO SPD. QUENCH
Advanced 0.00 to 200.00 % 0.50% hw
116 RO Health Store ALARM STATUS Alarms 0x0000 to 0xFFFF 0x0000 d8 Output
115 RO Health Word ALARM STATUS Alarms 0x0000 to 0xFFFF 0x0200 d7 Output
528 RO Last Alarm ALARM STATUS Alarms 0x0000 : No Active Alarms
0x0001 : Over Speed
0x0002 : Missing Pulse
0x0004 : Field Over I
0x0008 : Heatsink Trip
0x0010 : Thermistor
0x0020 : Over Volts (VA)
0x0040 : SPD Feed back
0x0080 : Encoder Failed
0x0100 : Field Failed
0x0200 : 3 Phase Failed
0x0400 : Phase Lock
0x0800 : 5703 RCV Error
0x1000 : Stall Trip
0x2000 : Over I Trip
0xf005 : External Trip
0x8000 : Accts Failed
0xf001 : Autotune Error
0xf002 : Autotune Aborted
0xf200 : Config Enabled
0xf400 : No Keypad
0xf006 : Remote Trip
0xff05 : PCB Version
0xff06 : Product Code
No Active Alarms oo Output, 1