B-14 Parameter Table MN792
Table B-2 Parameters Listed by Name Continued
Tag R/W Name Keypad Menu WB Block Range Factory Setting MN Notes
240 RW Max Value SYSTEM::CONFIGURE I/O::ANALOG INĆ
PUTS::ANIN 4 (A5)
Analog Input 4 -300.00 to 300.00 % 100.00% go
243 RW Max Value SYSTEM::CONFIGURE I/O::ANALOG INĆ
PUTS::ANIN 5 (A6)
Analog Input 5 -300.00 to 300.00 % 200.00% gr
259 RW Max Value SETUP PARAMETERS::RAISE/LOWER Raise/Lower -300.00 to 300.00 % 100.00% h7
178 RW MAX VOLTS SETUP PARAMETERS::FIELD CONĆ
TROL::FLD.CURRENT VARS::FLD.WEAK VARS
Field Control 0.00 to 100.00 % 100.00% ey
358 RW Min Demand SETUP PARAMETERS::SPEED LOOP::SETĆ
POINTS
Speed Loop -105.00 to 105.00 % -105.00% jy
179 RW MIN FLD.CURRENT SETUP PARAMETERS::FIELD CONĆ
TROL::FLD.CURRENT VARS::FLD.WEAK VARS
Field Control 0.00 to 100.00 % 10.00% ez 2
474 RW MIN PROFILE GAIN SETUP PARAMETERS::SPECIAL BLOCKS::PID PID 0.00 to 100.00 % 20.00% n6
126 RW MIN SPEED SETUP PARAMETERS::RAMPS Ramps 0.00 to 100.00 % 0.00% di
232 RW Min Value SYSTEM::CONFIGURE I/O::ANALOG INĆ
PUTS::ANIN 1 (A2)
Analog Input 1 -300.00 to 300.00 % -100.00% gg
235 RW Min Value SYSTEM::CONFIGURE I/O::ANALOG INĆ
PUTS::ANIN 2 (A3)
Analog Input 2 -300.00 to 300.00 % -100.00% gj
238 RW Min Value SYSTEM::CONFIGURE I/O::ANALOG INĆ
PUTS::ANIN 3 (A4)
Analog Input 3 -300.00 to 300.00 % -100.00% gm
241 RW Min Value SYSTEM::CONFIGURE I/O::ANALOG INĆ
PUTS::ANIN 4 (A5)
Analog Input 4 -300.00 to 300.00 % -100.00% gp
244 RW Min Value SYSTEM::CONFIGURE I/O::ANALOG INĆ
PUTS::ANIN 5 (A6)
Analog Input 5 -300.00 to 300.00 % -200.00% gs
258 RW Min Value SETUP PARAMETERS::RAISE/LOWER Raise/Lower -300.00 to 300.00 % -100.00% h6
130 RW Mode SERIAL LINKS::SYSTEM PORT (P3)::P3 SETĆ
UP
System Port P3 0 : Disabled
1 : 5703 Master
2 : 5703 Slave
3 : CELite (EIASCII)
0 dm
228 RW Mode SETUP PARAMETERS::JOG/SLACK Jog/Slack 0 : False 1 : True FALSE gc
268 RW Mode SETUP PARAMETERS::SPEED LOOP::ADĆ
VANCED::ADAPTION
Advanced 0 to 3 0 hg
473 RW Mode SETUP PARAMETERS::SPECIAL BLOCKS::PID PID 0 to 4 0 n5
43 RW Modulus SYSTEM::CONFIGURE I/O::DIGITAL OUTĆ
PUTS::DIGOUT 1 (B5)
Digout 1 (B5) 0 : False 1 : True TRUE b7
44 RW Modulus SYSTEM::CONFIGURE I/O::DIGITAL OUTĆ
PUTS::DIGOUT 2 (B6)
Digout 2 (B6) 0 : False 1 : True TRUE b8
45 RW Modulus SYSTEM::CONFIGURE I/O::DIGITAL OUTĆ
PUTS::DIGOUT 3 (B7)
Digout 3 (B7) 0 : False 1 : True TRUE b9
362 RW Modulus SYSTEM::CONFIGURE I/O::ANALOG OUTĆ
PUTS::ANOUT 1 (A7)
Analog Output 1 0 : False 1 : True FALSE k2
363 RW Modulus SYSTEM::CONFIGURE I/O::ANALOG OUTĆ
PUTS::ANOUT 2 (A8)
Analog Output 2 0 : False 1 : True FALSE k3
48 RW NEG. I CLAMP SETUP PARAMETERS::CURRENT LOOP Current Loop -100.00 to 100.00 % 0.00% bc
88 RO NEG. I CLAMP DIAGNOSTICS Diagnostics xxx.xx % (h) -90.0% cg Output
406 RW Negative Limit SETUP PARAMETERS::SPECIAL BLOCKS::PID PID -105.00 to 0.00 % -100.00% la
521 RW NOM Motor Volts CONFIGURE DRIVE Calibration 100 to 875 Volts 500 Volts oh 3
407 RW O/P SCALER(TRIM) SETUP PARAMETERS::SPECIAL BLOCKS::PID PID -3.0000 to 3.0000 0.2000 lb
464 RW Offset SYSTEM::CONFIGURE I/O::ANALOG OUTĆ
PUTS::ANOUT 1 (A7)
Analog Output 1 -100.00 to 100.00 % 0.00% mw
465 RW Offset SYSTEM::CONFIGURE I/O::ANALOG OUTĆ
PUTS::ANOUT 2 (A8)
Analog Output 2 -100.00 to 100.00 % 0.00% mx
212 RO Operating Mode DIAGNOSTICS Jog/Slack 0 : Stop
1 : Stop
2 : Jog Sp. 1
3 : Jog Sp. 2
4 : Run
5 : Take Up Sp. 1
6 : Take Up Sp. 2
7 : Crawl
Stop fw Output